Technical data
1592022750 Quick reference guide IC 200CX  Rel. 1.1 25/05/2009 
Pr1 
Password  0  999     
Pr2 
Password  0  999     
Pr3 
Password  0  999     
Defrost 
Param
eter 
Description  min  max  udm  Risolu
zione 
dF 1 
Defrost configuration: 
0= Not enabled 
1= Temperature / pressure 
2= start depends on par. dF24 stop for time duration 
3= start depends on par. dF24 stop for external contact 
4= defrost with condenser fan 
0  4     
dF 2 
Temperature or pressure of the defrost start-up 
-50.0 
-58 
0.0 
0 
70.0 
158 
50.0 
725 
°C 
°F 
bar 
psi 
Dec 
int 
Dec 
Int 
dF 3 
Temperature or pressure of the defrost stop  -50.0 
-58 
0.0 
0 
70.0 
158 
50.0 
725 
°C 
°F 
bar 
psi 
Dec 
int 
Dec 
Int 
dF 4 
Minimum defrost duration  0  250  Sec   
dF 5 
Maximum defrost duration  1  250  Min   
dF 6 
Time delay between the defrost of two circuits  0  250  Min   
dF 7 
OFF compressor delay before the defrost  0  250  Sec   
dF 8 
OFF compressor delay after the defrost  0  250  Sec   
dF 9 
Defrost interval time of the same circuit  1  99  Min   
dF 10
Temperature  setpoint  for  combined  defrost  of  the  1
st 
circuit  after 
parameter DF10 counting 
-50.0 
-58 
70.0 
158 
°C 
°F 
Dec 
int 
dF 11
Temperature setpoint for combined defrost end of the 1
st 
circuit.  -50.0 
-58 
70.0 
158 
°C 
°F 
Dec 
int 
dF 12
Temperature  setpoint  for  combined  defrost of  the  2
nd 
circuit  after 
parameter DF10 counting 
-50.0 
-58 
70.0 
158 
°C 
°F 
Dec 
int 
dF 13
Temperature setpoint for combined defrost end of the 2
nd 
circuit  -50.0 
-58 
70.0 
158 
°C 
°F 
Dec 
int 
dF 14
Activation of all the steps of the 1
st 
circuit during the defrost 
0= Not enabled 
1= Enabled 
0  1     
dF 15
Activation of all the steps of the 2
nd 
circuit during the defrost 
0= Not enabled 
1= Enabled 
0  1     
dF 16
Delay between  two compressor activation in defrost (compressors of 
the same circuit) 
0  250  Sec   
dF 17
Fan control during defrost / dripping time 
0= Not enabled 
1= Only in defrost 
2= For both functions defrost / dripping time 
0  2     
dF 18
Pressure / temperature setpoint to force the ventilation ON during the 
defrost. 
-50.0 
-58 
0.0 
0 
70.0 
158 
50.0 
725 
°C 
°F 
bar 
psi 
Dec 
int 
Dec 
Int 
Forced defrost 
dF 19
Minimum time delay before a forced defrost  0  250  sec   
dF 20
Pressure / temperature setpoint for a forced defrost  -50.0 
-58 
0.0 
0 
70.0 
158 
50.0 
725 
°C 
°F 
bar 
psi 
Dec 
int 
Dec 
int 