Technical data
1592022750 Quick reference guide IC 200CX  Rel. 1.1 25/05/2009 
Ar 7   
Probe  selection  for  antifreeze  heaters  /  integration  heating  in  Heat 
Pump mode 
0= Not enabled 
1= Evaporator inlet. 
2= Evaporator outlet 1 and 2. 
3= Evaporator outlet 1 and 2 and common outlet. 
0  3     
Ar 8   
Thermoregulation probe for anti-freeze / condenser heaters. 
0= not enabled. 
1= Condenser common water inlet probe. 
2= Condenser common water inlet and condenser inlet 1 / 2 probe. 
3= Condenser water outlet 1 / 2 probe. 
4= Condenser water outlet 1 / 2 and common outlet. 
0  4     
Ar 9   
Anti-freeze heaters control with unit in remote OFF or stand-by mode: 
0= Control not enable 
1=Controlled by anti-freeze thermoregulation. 
0  1     
Ar 10  
Anti-freeze heaters control for condenser/evaporator faulty probe: 
0= Anti-freeze heaters OFF 
1= Anti-freeze heaters ON 
0  1     
Boiler function 
Ar 11  
Boiler function 
0=Not enabled 
1=Enabled for integration heating 
2= Enabled for heating 
0  2     
Ar 12  
External air temperaure setpoint for boiler heaters  -50.0 
-58 
70.0 
158 
°C 
°F 
Dec 
int 
Ar 13  
Temperature differential for boiler heaters  0 
0 
25.0 
45 
°C 
°F 
Dec 
int 
Ar 14  
Time delay before turning the boiler on  0  250    Min 
Boiler function in Chiller mode 
Ar 15  
Setpoint for boiler heaters in chiller  50.0 
-58 
70.0 
158 
°C 
°F 
Dec 
int 
Ar 16  
Proportional band for boiler heaters in chiller  0.1 
0 
25.0 
45 
°C 
°F 
Dec 
int 
Boiler function in heat pump 
Ar 17  
Setpoint for boiler heaters in Heat Pump  50.0 
-58 
70.0 
158 
°C 
°F 
Dec 
int 
Ar 18  
Proportional band for boiler heaters in Heat Pump  0.1 
0 
25.0 
45 
°C 
°F 
Dec 
int 
Ar 19  
External air setpoint to stop the compressor as integration function  50.0 
-58 
70.0 
158 
°C 
°F 
Dec 
int 
Ar 20  
External air differential to stop the compressor as integration function  0.1 
0 
25.0 
45 
°C 
°F 
Dec 
int 
Water pumps on OFF or STD-BY 
Ar 21  
Water pump in OFF/ stand-by 
0= Aways in OFF 
1= ON only with antifreeze thermoregulation control 
0  1     
Ar 22  
Termoregulation probe water pump in antifreeze mode 
0= Not enabled 
1= Evaporator inlet 
2= Evaporator outlet 1 and 2 
3= Evaporator outlet 1 and 2 and common outlet 
4= External temperature 
0  4     
Ar 23  
Set point for water pump activation 
-50.0 
-58 
70.0 
158 
°C 
°F 
Dec 
int 
Ar 24  
Differential for water pump deactivation  0.1 
1 
25.0 
45 
°C 
°F 
Dec 
int 