Technical data
1592022750 Quick reference guide IC 200CX  Rel. 1.1 25/05/2009 
US 22
Temperature to activate geothermal function  0.1 
1 
0.0 
0 
25.0 
45 
14.0 
203 
°C 
°F 
Bar 
Psi 
Dec 
int 
Dec 
int 
US 23
Differential to deactivate geothermal function 
0.1 
1 
0.0 
0 
25.0 
45 
14.0 
203 
°C 
°F 
Bar 
Psi 
Dec 
int 
Dec 
int 
US 24
Time to activate/deactivate geothermal function 
0  250  sec   
US 25
Probe 1 selection (Pb1..Pb6) for geothermal function  0  6     
US 26
Probe 2 selection (Pb1..Pb6) for geothermal function  0  6     
US 27
Probes configuration for geothermal function 
0= Probe 1 for geothermal function – probe 2 for geothermal function 
1= Probe 2 for geothermal function – probe 1 for geothermal function 
0  1     
US 28
Geothermal function set point  -50.0 
-58 
0 
0 
70.0 
158 
50.0 
725 
°C 
°F 
Bar 
Psi 
Dec 
int 
Dec 
int 
US 29
Geothermal function differential 
0.1 
1 
0.0 
0 
25.0 
45 
14.0 
203 
°C 
°F 
Bar 
Psi 
Dec 
int 
Dec 
int 
US 30
Direct / reverse action for geothermal function 
0= direct action 
1= reverse action 
0  1     
US 31
Minimum value for geothermal function  0  US32
%   
US 32
Maximum value for geothermal function  US31
100  %   
Pr1 
Password  0  999     
Pr2 
Password  0  999     
Pr3 
Password  0  999     
Condenser fan 
Param
eters 
Description  min  max  M. U.  Resolu
tion 
FA 1   
Fan configuration output 
0 = Not enabled 
1 = Always on 
2 = ON/OFF regulation with steps 
3 = ON/OFF Continuous regulation 
4 = Proportional speed control 
0  4     
FA 2   
Fan operating mode 
0= Dependent from the compressor 
1= Independent from the compressor 
0  1     
FA 3   
Operation time at maximun speed when the fans start  0  250  Sec   
FA 4   
Phase shifting of the fan motor 
0  8 
Micro 
Sec 
250µs 
FA 5   
Number of condensing circuits 
0= one condenser circuit 
1= two condenser circuits 
0  1     
FA 6   
Pre-ventilation time before turning on the compressor in chiller mode  0  250  Sec   
Fan in Chiller mode 
FA 7   
Minimum speed for condenser fan in Chiller mode.  
To set  the minimum fan  speed percentage value  (30..100%), it  is 
related to the fan power supply. 
30  100  %   