US 6  
Probe selection for for auxiliary relay 2 control. Allows to select which 
probe value Pb1..Pb6 controls the relay 
1  6     
US 7  
Auxiliary relay 2 setpoint 
-50.0 
-58 
0.0 
0 
70.0 
158 
50.0 
725 
°C 
°F 
Bar 
Psi 
Dec 
int 
Dec 
int 
US 8  
Auxiliary relay 2 differential 
0.1 
1 
0.0 
0 
25.0 
45 
14.0 
203 
°C 
°F 
Bar 
Psi 
Dec 
int 
Dec 
int 
Auxiliary proportional output n° 1 
US 9  
Auxiliary proportional output n° 1 operating mode 
0= Not enabled 
1= Always available with direct action 
2= Available only when the unit is on with direct action 
3= Always available with reverse action 
4= Available only when the unit is on with reverse action 
0  4     
US 10
Probe selection for auxiliary proportional output 1 
Allows to select which probe value Pb1..Pb6 controls output 
1  6     
US 11
Minimum value of the auxiliary proportional output 1 
0  US12
%   
US 12
Maximum value of the auxiliary proportional output 1 
US11
100  %   
US 13
Auxiliary proportional output 1 setpoint 
-50.0 
-58 
0.0 
0 
70.0 
158 
50.0 
725 
°C 
°F 
Bar 
Psi 
Dec 
int 
Dec 
int 
US 14
Auxiliary proportional output 1 differential 
0.1 
1 
0.0 
0 
25.0 
45 
14.0 
203 
°C 
°F 
Bar 
Psi 
Dec 
int 
Dec 
int 
Auxiliary proportional output n° 2 
US 15
Auxiliary proportional output n° 2 operating mode 
0= Not enabled 
1= Always available with direct action 
2= Available only when the unit is on with direct action 
3= Always available with reverse action 
4= Available only when the unit is on with reverse action 
0  4     
US 16
Probe selection for auxiliary proportional output 2 
Allows to select which probe value Pb1..Pb10 controls output 
1  6     
US 17
Minimum value proportional output 2 
0  US18
%   
US 18
Maximum value proportional output 2 
US17
100  %   
US 19
Auxiliary setpoint proportional output 2 
-50.0 
-58 
0.0 
0 
70.0 
158 
50.0 
725 
°C 
°F 
Bar 
Psi 
Dec 
int 
Dec 
int 
US 20
Differenzential proportional output 2 
0.1 
1 
0.0 
0 
25.0 
45 
14.0 
203 
°C 
°F 
Bar 
Psi 
Dec 
int 
Dec 
int 
Geothermal function 
US 21
Geothermal function activation 
0= only in chiller 
1= only in heat pump 
2= chiller and heat pump 
0  2     