Technical data
1592022750 Quick reference guide IC 200CX  Rel. 1.1 25/05/2009 
CO 83
Probe  selection  (Pb1..Pb6) for  modulating condenser  water  pump  in 
chiller 
0  6     
CO 84
Probe  selection  (Pb1..Pb6) for  modulating condenser  water  pump  in 
heat pump 
0  6     
CO 85
Set point for modulating condenser water pump in chiller  -50.0 
-58 
0 
0 
70.0 
158 
50.0 
725 
°C 
Int 
Dec 
int 
CO 86
Proportional band for modulating condenser water pump in chiller  0.1 
1 
0.1 
1 
25.0 
45 
14.0 
203 
°C 
Int 
Dec 
int 
CO 87
Set point for modulating condenser water pump in heat pump  -50.0 
-58 
0 
0 
70.0 
158 
50.0 
725 
°C 
Int 
Dec 
int 
CO 88
Proportional  band  for  modulating  condenser  water  pump  in  heat 
pump 
0.1 
1 
0.1 
1 
25.0 
45 
14.0 
203 
°C 
Int 
Dec 
int 
CO 89
Minimun value of the signal for the modulation of the pump  0  CO90
%   
CO 90
Maximun value of the signal for the modulation of the pump  CO89
100  %   
CO 91
Time at maximum speed when the pump is activated  0  250  sec   
CO 92
Value of the signal when the compressor is OFF or when the unit is in 
STD-BY or remote OFF 
0  100  %   
CO 93
Time at maximum speed during the switching off of the pump  0  250  sec   
Pr1 
Password  0  999     
Pr2 
Password  0  999     
Pr3 
Password  0  999     
Auxiliary relay 
Param
eters 
Description  min  max  M. U.  Resolu
tion 
Auxiliary relay of the circuit 1 
US 1  
Auxiliary relay 1 operating mode 
0= Not enabled 
1= Always available with direct action 
2= Available only when the unit is on with direct action 
3= Always available with reverse action 
4= Available only when the unit is on with reverse action 
0  4     
US 2  
Probe  selection  for  auxiliary  relay  1  control.  Allows  to  select  which 
probe Pb1..Pb6 controls the relay 
1  6     
US 3  
Auxiliary relay 1 setpoint 
-50.0 
-58 
0.0 
0 
70.0 
158 
50.0 
725 
°C 
°F 
Bar 
Psi 
Dec 
int 
Dec 
int 
US 4  
Auxiliary relay 1 differential 
0.1 
1 
0.0 
0 
25.0 
45 
14.0 
203 
°C 
°F 
Bar 
Psi 
Dec 
int 
Dec 
int 
Auxiliary relay circuit 2 
US 5  
Auxiliary relay 2 operating mode 
0= Not enabled 
1= Always available with direct action 
2= Available only when the unit is on with direct action 
3= Always available with reverse action 
4= Available only when the unit is on with reverse action 
0  4     