Technical data
1592022750 Quick reference guide IC 200CX  Rel. 1.1 25/05/2009 
CO 37
Maximum  unloading  duration  time to  keep  activated  the  Unloading 
function from high temperature of the evaporator water inlet  (See 
unloading function). 
0  250  Min   
CO 38
Unloading  compressor  setpoint  in  chiller  to  prevent  low  temperature 
of the evaporator water inlet (See unloading function). 
-50 
-58 
70.0 
158 
°C 
°F 
Dec 
int 
CO 39
Unloading  Differential  to  prevent  low  temperature  of  the  evaporator 
water inlet (See unloading function). 
0.1 
1 
25.0 
45 
°C 
°F 
Dec 
int 
CO 40
Maximum  unloading  duration  time to  keep  activated  the  Unloading 
function from low temperature of the  evaporator water inlet  (See 
unloading function). 
0  250  Min   
Condenser Unloading 
CO 41
Unloading  compressor  setpoint.  From  temperature  /  pressure  in 
chiller mode (See unloading function). 
0 
0 
50.0 
725 
Bar 
psi 
Dec 
int 
CO 42
Unloading  Differential.  From  temperature  /  pressure  in  chiller  mode 
(See unloading function). 
0.0 
0 
14.0 
203 
Bar 
Psi 
Dec 
int 
CO 43
Unloading  compressor  setpoint.  From  temperature  /  pressure  in  HP 
mode (See unloading function). 
0 
0 
50.0 
725 
Bar 
psi 
Dec 
int 
CO 44
Unloading Differential. From temperature / pressure in HP mode (See 
unloading function). 
0.0 
0 
14.0 
203 
Bar 
Psi 
Dec 
int 
CO 45
Maximum unloading duration time from temperature/pressure control.  0  250  Min   
CO 46
Number of steps for circuit with active unloading 
1= 1
st
 step 
2= 2
nd
 step 
3= 3
rd
 step 
1  3     
CO 47
Minimum  ON  time  of  the  capacity  step  after  the  unloading  function 
start (only for capacity compressor) 
0  250  Sec   
Compressor liquid injection 
CO 48
Setpoint of the solenoid valve (on) of the liquid injection 
0 
32 
150 
302 
°C 
°F 
Dec / 
int 
int 
CO 49
Setpoint of the solenoid valve (off) of the liquid injection  0.1 
1 
25.0 
45 
°C 
°F 
Dec 
int 
Load management in neutral zone 
CO 50
Maximum working time in neutral zone without steps insertion  0  250  Min  10 Min 
CO 51
Maximum working time in neutral zone without steps rotation  0  999  Hr  1Hr 
Pump down to time 
CO 52
Maximum  time  for  the  activation  of  the  pump-down  during  the 
switching off 
CO58 = 0 Not enabled 
0  250  Sec   
CO 53
Maximum  time  for  the  activation  of  the  pump-down  during  the 
switching on 
CO59 = 0 Not enabled 
0  250  Sec   
Compressor inverter controlled 
CO 54
Time at maximum speed during compressor start up 
0  250  sec   
CO 55
Minimum value of the proportional output at compressor start up 
0  100  %   
CO 56
Minimum interval time of the capacity variation at compressor start up  1  250  sec   
CO 57
Value under wich starts counting time CO58  0  100  %   
CO 58
Maximum working time of the compressor with percentage lower than 
CO57 
0  250  Min  10 Min 
CO 59
Time of forcing the compressor digital scroll to the maximum power 
0  250  sec  10sec 
CO 60
Maximum working time for compressors rotation 
0  999  Hr  1Hr 