CO 20
Operative mode of the condenser pump 
0= Not enabled 
1= ON/OFF: continuous operation type 1 
When the unit is running in Chiller or Heat Pump the pump is running. 
In std-by or remote OFF mode, the pump is OFF. 
2= ON/OFF: on if called by compressor 
When a compressor is running, the pump is running. 
3= ON/OFF: continuous operation type 2 
When the unit is  running in  Chiller  or Heat Pump or  in STD-By or  in 
OFF, the pump is running. 
4= Modulation: continuous operation type 1 
When the unit is running in Chiller or Heat Pump the pump is running. 
In std-by or remote OFF mode, the pump is OFF. 
5= Modulation: on if called by compressor 
When a compressor is running, the pump is running. 
6= Modulation: continuous operation type 2 
When the unit is  running in  Chiller  or Heat Pump or  in STD-By or  in 
OFF, the pump is running. 
0  6     
CO 21
Delay  time  to  switch  off  the  pump  starting  from  compressor 
deactivation or when the unit is placed in std-by 
0  250  Min   
CO 22
Number of running hours for condenser pump rotation  0  999  10Hr  10Hr 
CO 23
Contemporary working time of the pumps during rotation  0  250  Sec   
Load maintenance 
CO 24
Compressor 1: number of working hour to signalling maintenance 
warning 
0  999  10 Hr  10 Hr 
CO 25
Compressor 2: number of working hour to signalling maintenance 
warning 
0  999  10 Hr  10 Hr 
CO 26
Evaporator  pump  /  supply fan:  number  of  working  hour  to  signalling 
maintenance warning 
0  999  10 Hr  10 Hr 
CO 27
Support  evaporator  pump  /  supply  fan:  number  of  working  hour  to 
signalling maintenance warning 
0  999  10 Hr  10 Hr 
CO 28
Condenser pump: number of  working hour to signalling maintenance 
warning 
0  999  10 Hr  10 Hr 
CO 29
Support  condenser  pump:  number  of  working  hour  to  signalling 
maintenance warning 
0  999  10 Hr  10 Hr 
Pump down 
CO 30
Pump down operating mode (See pump down ON/OFF function) 
0= Not enabled 
1= Pump down enabled only during the switching off 
2= Pump down enabled during the switching off and switching on 
3= in Chiller mode pump down enabled only during the switching off 
4= in  Chiller mode  pump  down enabled during the switching  off  and 
switching on 
0  4     
CO 31
Pump–down pressure setpoint (See pump down ON/OFF function)  0 
0 
50.0 
725 
Bar 
psi 
Dec 
int 
CO 32
Pump-down pressure differential (See pump down ON/OFF function)  0 
0 
14.0 
203 
Bar 
psi 
Dec 
int 
CO 33
Maximum pump–down time  duration at start-up and stop (See pump 
down ON/OFF function) 
0  250  Sec   
Evaporator Unloading 
CO 34
Unloading compressor setpoint in chiller to  prevent high temperature 
of the evaporator water inlet (See unloading function). 
-50 
-58 
70.0 
158 
°C 
°F 
Dec 
int 
CO 35
Unloading Differential. From high temperature of the evaporator water 
inlet (See unloading function). 
0.1 
1 
25.0 
45 
°C 
°F 
Dec 
int 
CO 36
Delay time to engage the Unloading function from high temperature of 
the evaporator water inlet (See unloading function). 
0  250  Sec  10sec 