Technical data
1592022750 Quick reference guide IC 200CX  Rel. 1.1 25/05/2009 
ES 10
Thursday energy saving activated 
Automatic unit on-off 
0 - 0  7 - 7     
ES 11
Friday energy saving activated 
Automatic unit on-off 
0 - 0  7 - 7     
ES 12
Saturday energy saving activated 
Automatic unit on-off 
0 - 0  7 - 7     
ES 13
Sunday energy saving activated 
Automatic unit on-off 
0 - 0  7 - 7     
ES 14
Offset for Energy Saving function in chiller mode  -30.0 
-54 
30.0 
54 
°C 
°F 
Dec 
int 
ES 15
Differential for Energy Saving function in chiller  0.1 
1 
25.0 
45 
°C 
°F 
Dec 
int 
ES 16
Offeset for Energy Saving function in heat pump  -30.0 
-54 
30.0 
54 
°C 
°F 
Dec 
int 
ES 17
Differential for Energy Saving in heat pump  0.1 
1 
25.0 
45 
°C 
°F 
Dec 
int 
ES 18
Maximum working time of  the unit  when switched on from keyboard 
(and the unit is OFF by Energy saving) 
0= Not enabled 
0  250  Min  10 Min 
Pr1 
Password  0  999     
Pr2 
Password  0  999     
Pr3 
Password  0  999     
Compressors 
Param
eters 
Description  min  max  udm  Risolu
zione 
CO 1
Minimum compressor ON time after the start-up  0  250  10 sec
10 sec 
CO 2
Minimum compressor OFF time after the switching off  0  250  10 sec
10 sec 
CO 3
ON delay time between two compressors or compressor and valve. 
1  250  Sec   
CO 4
OFF delay time between two compressors or compressor and valve  0  250  Sec   
CO 5
Delay time to activate the thermoregulation starting from the power on  0  250  10 Sec
10 sec 
Partialization (Capacity Control) 
CO 6
Functioning (see Capacity Control) 
0= On/off steps 
1= Continuous insertion of the steps and direct action 
2= Continuous insertion of the steps and reverse action 
3= Continuous insertion of the steps 
0  3     
CO 7
Start-up with minimum compressor power / automatic start-unloading 
valve 
0 = Only at the compressor start-up (Minimum power automatic start-
unloading valve off) 
1=  At  the  compressor  start-up  and  during  the  termoregulation 
(Minimum power / automatic start-unloading valve off) 
2 = Only at the screw compressor start-up (Minimum power automatic 
start-unloading valve off) 
3=  At  the  compressor  start-up  and  during  the  termoregulation 
(Minimum power / Unloading valve ON with compressor off) 
0  3     
CO 8
ON time of the intermittent solenoid valve for screw compressor 
0= the function is not enabled 
0  250  Sec   
CO 9
OFF time of the inetrmittent solenoid valve for screw compressor  0  250  Sec   
Compressor start-up 
CO 10
Compressor start-up selection 
0= Direct 
1= Part - winding 
0  1     