Technical data
1592022750 Quick reference guide IC 200CX  Rel. 1.1 25/05/2009 
CF 54
Power supply frequency 
0= disabled 
1= Frequency 50 Hz and only signalling alarm 
2= Frequency 50 Hz and alarm (all output OFF in case of alarm) 
3= Frequency 60 Hz and only signalling alarm 
4= Frequency 60 Hz and alarm (all output OFF in case of alarm) 
(ATTENTION: if  the  condenser  fan is  not controlled  by  cut  of  phase 
signal (PWM) the parameter  CF54 can be configured at 0 value and 
the frequency alarm is not enabled) 
0  4     
Serial Address 
CF 55
Serial address  1  247     
CF 56
Firmware Release (this parameter is only in reading)         
CF 57
Eeprom parameter map (this parameter is only in reading)         
Enabling compressors 
CF 58
Enabling compressors 
0= chiller and heat pump 
1= only chiller 
2= only heat pump 
0  2     
Pr1 
Password  0  999     
Pr2 
Password  0  999     
Pr3 
Password  0  999     
Dynamic Setpoint 
Param
eters 
Description  min  max  M. u.  Resolu
tion 
Sd 1   
Maximum offset for dynamic setpoint function in chiller  -30.0 
-54 
30.0 
54 
°C 
°F 
Dec 
int 
Sd 2   
Maximum offset for dynamic setpoint function in heat pump  -30.0 
-54 
30.0 
54 
°C 
°F 
Dec 
int 
Sd 3   
Setpoint of outside temperature for dynamic setpoint function in chiller  -50.0 
-58 
70.0 
158 
°C 
°F 
Dec 
int 
Sd 4   
Setpoint of outside temperature for dynamic setpoint function in heat 
pump 
-50.0 
-58 
70.0 
158 
°C 
°F 
Dec 
int 
Sd 5   
Differential of  outside temperature for  dynamic setpoint  function  in 
chiller 
-30.0 
-54 
30.0 
54 
°C 
°F 
Dec 
int 
Sd 6   
Differential of  outside temperature for  dynamic setpoint  function  in 
heat pump 
-30.0 
-54 
30.0 
54 
°C 
°F 
Dec 
int 
Pr1 
Password  0  999     
Pr2 
Password  0  999     
Pr3 
Password  0  999     
Energy saving 
Param
eters 
Description  min  max  udm  Risolu
zione 
ES 1   
Start of the Time band 1 (0÷24)  0  24.00
Hr  10 Min 
ES 2   
End of the Time Band 1 (0÷24)  0  24.00
Hr  10 Min 
ES 3   
Start of the Time band 2 (0÷24)  0  24.00
Hr  10 Min 
ES 4   
End of the Time Band 2 (0÷24)  0  24.00
Hr  10 Min 
ES 5   
Start of the Time band 3 (0÷24)  0  24.00
Hr  10 Min 
ES 6   
End of the Time Band 3 (0÷24)  0  24.00
Hr  10 Min 
ES 7   
Monday: energy saving activated 
Automatic unit on-off 
0 - 0  7 - 7     
ES 8   
Tuesday energy saving activated 
Automatic unit on-off 
0 - 0  7 - 7     
ES 9   
Wednesday energy saving activated 
Automatic unit on-off 
0 - 0  7 - 7     