Technical data
1592022750 Quick reference guide IC 200CX  Rel. 1.1 25/05/2009 
13 TABLE OF THE PARAMETERS 
Thermoregulation 
Par  Description  min  max  u.m. 
Resol
ution 
ST 1   
Chiller Setpoint 
Allow to modify the setpoint of the unit in chiller mode 
ST02  ST03  °C/°F  dec/int 
ST 2   
Chiller minimum Setpoint 
Minimum setpoint limit for ST 1 
-50.0 
-58 
ST01 
°C 
°F 
dec/int 
ST 3   
Chiller maximum Setpoint 
Maximum setpoint limit for ST 1 
ST01 
70.0 
158 
°C 
°F 
dec/int 
ST 4   
Heat pump setpoint 
Allow to modify the setpoint of the unit in heat pump mode 
ST05  ST06  °C/°F  dec/int 
ST 5   
Heat pump minimum Setpoint 
Minimum setpoint limit for ST 4 
-50.0 
-58 
ST04 
°C 
°F 
Dec 
int 
ST 6   
Heat pump maximum Setpoint 
Maximum setpoint limit for ST 4 
ST04 
70.0 
158 
°C 
°F 
Dec 
int 
ST 7   
Regulation band in chiller mode  0.0 
0 
25.0 
45 
°C 
°F 
Dec 
int 
ST 8   
Regulation band in heat pump mode  0.0 
0 
25.0 
45 
°C 
°F 
Dec 
int 
ST 9   
Thermoregulation probe selection in chiller 
0= Temperature probe NTC for evaporator inlet 
1= Temperature probe NTC for evaporator outlet 1  
2= Temperature probe NTC for evaporator outlet 2 
3= Temperature probe NTC for common evaporator outlet 
4= Temperature NTC probe from remote keyboard 1 
5= Temperature NTC probe from remote keyboard 2 
0  5     
ST 10
Thermoregulation probe selection in heat pump 
0= Temperature probe NTC for evaporator inlet 
1= Temperature probe NTC for evaporator outlet 1  
2= Temperature probe NTC for evaporator outlet 2 
3= Temperature probe NTC for common evaporator outlet 
4= Temperature NTC probe from remote keyboard 1 
5= Temperature NTC probe from remote keyboard 2 
6= Temperature probe for water common inlet of the condenser 
7= Temperature probe for water inlet of the circuit # 1 condenser 
8= Temperature probe for water inlet of the circuit # 2 condenser 
9= Temperature probe for water outlet of the circuit # 1 condenser 
10= Temperature probe for water outlet of the circuit # 2 condenser 
11= Temperature probe for water common outlet of the condenser 
ATTENTION 
To have the same thermoregulation for chiller  and heat pump mode, 
set the parameters ST09 and ST10 with the same value 
0  11     
ST 11
Type of thermoregulation 
0= Proportional 
1= Neutral zone 
0  1     
ST 12
Set point for change over function  -50.0 
-58 
70.0 
158 
°C 
°F 
Dec 
Int 
ST 13
Differential for change over function  0.1 
1 
25.0 
45 
°C 
°F 
Dec 
Int 
Pr1 
Password  0  999     
Pr2 
Password  0  999     