Technical data
1592022750 Quick reference guide IC200CX  Rel. 1.1 25/05/2009 
b(n)lP  Low condensing temperature NTC circuit (n) 
Yes    Yes   
b(n)tF 
Fan overload circuit (n) 
Yes    Yes   
b(n)PH
Pump down alarm in stop regulation of the circuit (n) 
Yes   
Yes 
b(n)PL
Pump down in regulation start-up of the circuit (n) 
Yes   
Yes 
b(n)dF 
Bad defrost circuit (n) 
b(n)Cu 
Unloading from condenser high temp/press of the circuit (n) 
b(n)Cu
Unloading from evaporator low temp/press of the circuit (n) 
Yes   
Yes 
b(n)rC 
Recovery function disabled in circuit (n) 
b(n)ds 
Circuit (n) disabled from keyboard 
Yes   
Yes 
b(n)Ac
Anti-freeze circuit (n) message in chiller 
b(n)Ah
Anti-freeze circuit (n) message in heat pump 
(n) identifies the circuit 1 or 2 
12.3  ALARM: āCā TYPE AND STATUS OF THE LOADS IN CASE OF ALARM 
Alarm 
Code 
Alarm description  Compressor 
(n) 
Compressors not involved 
C(n)HP
Compressor(n) high pressure switch  Yes   
C(n)oP 
Compressor(n) oil pressure switch / Oil level switch  Yes   
C(n)tr 
Compressor(n) overload  Yes   
C(n)dt 
Compressor high discharge temperature  Yes   
C(n)dS 
Compressor (n) disabled from keyboard  Yes   
C(n)Mn
Compressor(n) maintenance     
(n) identifies the compressor 1, 2 , 3 , 4 , 5 , 6 