Technical data
1592022750 Quick reference guide IC 200CX  Rel. 1.1 25/05/2009 
11.5   ERASE THE ALARM LOG LIST 
ALOG FUNCTION TO ERASE THE LOG LIST 
1.  Enter the function Menu. 
2.  Use the UP or DOWN keys to select ALOG on the bottom display. 
3.  Push the SET key. 
4.  Push UP or DOWN keys and search the ArSt label on the bottom display; the top display shows 
PAS. 
5.  Push SET: the bottom display shows PAS and the top display shows 0 value blinking. 
6.  Insert the password 
7.  If  the  password  is  OK  the  label  ArST  blinks  for  5  seconds  then  the  display  returns  to  normal 
condition read-out (probes). 
8.  If the password is not correct the display shows PAS again. in any case is possible to scroll the 
list with UP or DOWN 
9.  To exit push the M key one time or wait the timeout. 
11.6  PASSWORD VALUE OF THE ALARM LIST 
The default value is 0 to change this value enter Pr3 level under the AL parameter family. 
THE  ALARM  LIST  CONTAINS  100  EVENTS  IN  A  FIFO  STRUCTURE.  WHEN  THE  MEMORY  IS 
FULL ANY NEW ALARM WILL ERASE THE OLDEST. 
11.7  DISABLE – ENABLE A SINGLE CIRCUIT 
Through the instruments keyboard is possible to completely disable a single circuit for maintenance or 
to use just a cooling part of of the unit. 
CrEn FUNCTION enables – disables a circuit from keyboard. 
Label involved with CrEn function: Cr1E = circuit 1, Cr2E = circuit 2 
HOW TO DISABLE A CIRCUIT 
Enter the function Menu 
1.  Use UP or DOWN keys to select CrEn on the bottom display 
2.  Push SET key: the bottom display = Cr1E, top display = En. 
3.  Select the circuit 1 or 2 with UP or DOWN key (Cr1E or Cr2E). 
4.  Push  SET key  for  3  seconds  when;  the  top  display  shows  the  En  blinking  label.  Using  UP  or 
DOWN key, choose the label diS (Disabled) or En (Enabled), then push SET key to confirm the 
new selection. The display shows next circuit status. 
5.  To exit the CrEn function push MENU key or wait the timeout. 