Technical data

1592022750 Quick reference guide IC 200CX Rel. 1.1 25/05/2009
11.5 ERASE THE ALARM LOG LIST
ALOG FUNCTION TO ERASE THE LOG LIST
1. Enter the function Menu.
2. Use the UP or DOWN keys to select ALOG on the bottom display.
3. Push the SET key.
4. Push UP or DOWN keys and search the ArSt label on the bottom display; the top display shows
PAS.
5. Push SET: the bottom display shows PAS and the top display shows 0 value blinking.
6. Insert the password
7. If the password is OK the label ArST blinks for 5 seconds then the display returns to normal
condition read-out (probes).
8. If the password is not correct the display shows PAS again. in any case is possible to scroll the
list with UP or DOWN
9. To exit push the M key one time or wait the timeout.
11.6 PASSWORD VALUE OF THE ALARM LIST
The default value is 0 to change this value enter Pr3 level under the AL parameter family.
THE ALARM LIST CONTAINS 100 EVENTS IN A FIFO STRUCTURE. WHEN THE MEMORY IS
FULL ANY NEW ALARM WILL ERASE THE OLDEST.
11.7 DISABLE ENABLE A SINGLE CIRCUIT
Through the instruments keyboard is possible to completely disable a single circuit for maintenance or
to use just a cooling part of of the unit.
CrEn FUNCTION enables – disables a circuit from keyboard.
Label involved with CrEn function: Cr1E = circuit 1, Cr2E = circuit 2
HOW TO DISABLE A CIRCUIT
Enter the function Menu
1. Use UP or DOWN keys to select CrEn on the bottom display
2. Push SET key: the bottom display = Cr1E, top display = En.
3. Select the circuit 1 or 2 with UP or DOWN key (Cr1E or Cr2E).
4. Push SET key for 3 seconds when; the top display shows the En blinking label. Using UP or
DOWN key, choose the label diS (Disabled) or En (Enabled), then push SET key to confirm the
new selection. The display shows next circuit status.
5. To exit the CrEn function push MENU key or wait the timeout.