Technical data
1592022750 Quick reference guide IC 200CX  Rel. 1.1 25/05/2009 
8  ANALOG AND DIGITAL OUTPUT CONFIGURATION 
8.1  ANALOG INPUT PB1 - PB2 – PB5 – PB6 
Parameters involved: 
CF08 = Configuration PB1 
CF09 = Configuration PB2 
CF12 = Configuration PB5 
CF13 = Configuration PB6 
0.  Not enabled 
1.  Temperature probe PTC for compressor #1 discharge 
2.  Temperature probe NTC for evaporator inlet 
3.  Temperature probe NTC for evaporator #1 outlet 
4.  Temperature probe NTC for evaporator #2 outlet 
5.  Temperature probe NTC for common evaporator outlet 
6.  Temperature probe NTC for common hot water condenser inlet 
7.  Temperature probe NTC for hot water of the condenser circuit #1 inlet 
8.  Temperature probe NTC for hot water of the condenser circuit #2 inlet 
9.  Temperature probe NTC for hot water of the condenser circuit #1 outlet 
10.  Temperature probe NTC for hot water of the condenser circuit #2 outlet 
11.  Temperature probe NTC for hot water of the condenser common outlet 
12.  Temperature probe NTC (external temperature) for dynamic setpoint  / boiler / change over 
13.  Temperature probe NTC for combined defrost circuit #1 
14.  Temperature probe NTC for combined defrost circuit #2 
15.  Temperature probe NTC for auxiliary output #1 
16.  Temperature probe NTC for auxiliary output #2 
17.  Temperature probe NTC for condensing circuit #1 
18.  Temperature probe NTC for condensing circuit #2 
Every analogue input can be configured as digital input; after the number 18, the values o 1 … c38 
allow the configuration of  the  analogue input  as  digital  inputs with the  same  meaning  (o  1=  remote 
ON/OFF, o 2= Remote chiller / heat pump, …..). 
8.2  ANALOG INPUT CONFIGURATION PB3 - PB4 
Parameter involved: 
CF10 = Configuration PB3 
CF11 = Configuration PB4 
0  Not enabled 
1  Temperature probe PTC for compressor #1 discharge 
2  Temperature probe NTC for evaporator inlet 
3  Temperature probe NTC for evaporator #1 outlet 
4  Temperature probe NTC for evaporator #2 outlet 
5  Temperature probe NTC for common evaporator outlet 
6  Temperature probe NTC for common hot water condenser inlet 
7  Temperature probe NTC for hot water of the condenser circuit #1 inlet 
8  Temperature probe NTC for hot water of the condenser circuit #2 inlet 
9  Temperature probe NTC for hot water of the condenser circuit #1 outlet 
10  Temperature probe NTC for hot water of the condenser circuit #2 outlet 
11  Temperature probe NTC for hot water of the condenser common outlet 