Technical data
1592022750 Quick reference guide IC 200CX  Rel. 1.1 25/05/2009 
Push once 
To turn ON or turn OFF the controller (in chiller or 
heat pump depending from CF51 parameter) 
Push once  To enter the function Menu 
Push for 3 seconds  To set the clock (controller with clock on board) 
Pushing  once  during  the 
programming 
To exit from a group of parameter 
5.5  KEY COMBINANTION 
KEY  ACTION  FUNCTION 
Push for 3 seconds together  Enter the programming parameters 
Only  in  Pr3  level:  push  SET 
and DOWN key 
Select the parameter level visibility Pr1 / Pr2 / 
Pr3 
Push once together  Exit the programming parameters 
Push 5 seconds in heat pump 
mode 
Manual defrost 
Only  in  Pr3  programming 
level: push SET and then the 
MENU key 
In  Pr3  defines  if  the  parameter  can  be 
modified or not in the other levels. 
6  REMOTE TERMINAL 
The iCHILL can be connected to a remote keyboard (max 2 remote keyboards). 
The remote keyboard with probe on board can be used for the regulation of the machine. 
The maximum length of the cable is 150mt (shielded cable is recommended). 
Use the connection cable CAB/CJ30 (2x0.2 mm
2
) to interface the ichill connector to the shielded wire. 
In case of communication problems (hardware problems or bad connection) the upper display shows 
“noL” (no link). 