5  DISPLAY INFORMATION 
5.1  READ THE SET POINT VALUE 
Push and release the SET key, the set value is displayed. 
In stand-by the bottom display shows SetC (set chiller), by pushing SET again the next label is SetH 
(set heat pump). 
If the unit is running the only set displayed is related to the running mode. 
5.2  MODIFY THE SET POINT 
1)  Push SET key for at least 3 seconds 
2)  Use the UP or DOWN key to modify the setpoint. In chiller it is possible to modify the chiller set 
point,  in  heat  pump  it  is  possible  to  modify  the  heat  pump  set  point,  in  std-by  it  is  possible  to 
modify both the set point. 
3)  Push SET to confirm or wait the timeout (15seconds). 
5.3  READ  THE  ACTIVE  SETPOINT  DURING  ENERGY  SAVING  OR 
DYNAMIC SETPOINT 
If  the  unit  is  running  in  chiller  or  heat  pump,  the  Energy  Saving  or  the  Dinamic  Setpoint  activity  is 
signalled by the blinking of the Vset icon. 
Chiller  mode:  push  SET  one  time,  the  bottom  display  shows  the  SEtC  (set  chiller)  while  the  top 
display shows the  set  value. Only if the Energy saving  or the Dynamic  Setpoint  are active, pushing 
another time the SET key, the bottom display shows “SEtr” (real setpoint), and the top display shows 
the setpoint that the unit is really using for the thermoregulation. 
Heat pump mode: push SET one time, the bottom display shows the SEtH (set Heat pump) while the 
top display shows the set value. Only if the Energy saving or the Dynamic Setpoint are active, pushing 