Technical data
 Ichill 200CX EVO  rev 1.1  14/11/2013 
Pag. 99 of 151 
Label on alarm 
visualization menu
ACF9 
Recovery function enabled but whitout resources needed (condenser probe, 
digital input for recovery, valve for recovery) 
AC10 
Compressor inverter controlled 
• 2 anologue output configurated for the same compressor 
• One analog output is configured as output for compressor inverter 
controlled but none relays is configured as compressor 
• Parameter CF03=1 and one analog output configured as compressor 
inverter controlled 
AC11 
Compressor with different power capacity enabled and: 
• One analog output is configured as output for compressor inverter 
controlled 
• one of the compressor has capacity power = 0 
• the regulation is not a neutral zone 
AC12 
Free cooling function enabled and: 
•  None relay is configured as free cooling valve 
•  None probe is configured as evaporator inlet probe and free cooling 
probe 
•  wrong configuration of the following parameters: FS21 < FS22 
AC13 
Sanitary hot water function enabled and: 
•  None relay is configured as valve 1, valve 2 or domestic hot water pump 
•  None probe is configured as probe 1 and probe 2 for sanitary hot water 
production 
Origin 
Wrong programming 
Reset 
Correctly programming 
Restart 
Automatic 
Symbol 
On the display the symbol 
 is blinking 
Action 
Alarm relay + buzzer ON 
ArtF Clock failure 
Label on alarm 
visualization menu 
ArtF (clock failure) 
Origin 
Clock failure 
Reset 
Replace the instrument 
Restart 
Manual in function menu 
Symbol 
On the display the symbol 
 is blinking 
Action 
Alarm relay + buzzer ON 
Regulation 
Loads 
Not changed 
Energy saving 
Disabled if controlled by RTC 
Unit ON/OFF 
Disabled if controlled by RTC 
ArtC Clock alarm 
Label on alarm 
visualization menu 
ArtC (clock alarm) 
Origin 
Wrong setting 