Technical data

Ichill 200CX EVO rev 1.1 14/11/2013
Pag. 99 of 151
Label on alarm
visualization menu
ACF9
Recovery function enabled but whitout resources needed (condenser probe,
digital input for recovery, valve for recovery)
AC10
Compressor inverter controlled
2 anologue output configurated for the same compressor
One analog output is configured as output for compressor inverter
controlled but none relays is configured as compressor
Parameter CF03=1 and one analog output configured as compressor
inverter controlled
AC11
Compressor with different power capacity enabled and:
One analog output is configured as output for compressor inverter
controlled
one of the compressor has capacity power = 0
the regulation is not a neutral zone
AC12
Free cooling function enabled and:
None relay is configured as free cooling valve
None probe is configured as evaporator inlet probe and free cooling
probe
wrong configuration of the following parameters: FS21 < FS22
AC13
Sanitary hot water function enabled and:
None relay is configured as valve 1, valve 2 or domestic hot water pump
None probe is configured as probe 1 and probe 2 for sanitary hot water
production
Origin
Wrong programming
Reset
Correctly programming
Restart
Automatic
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer ON
ArtF Clock failure
Label on alarm
visualization menu
ArtF (clock failure)
Origin
Clock failure
Reset
Replace the instrument
Restart
Manual in function menu
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer ON
Regulation
Loads
Not changed
Energy saving
Disabled if controlled by RTC
Unit ON/OFF
Disabled if controlled by RTC
ArtC Clock alarm
Label on alarm
visualization menu
ArtC (clock alarm)
Origin
Wrong setting