Technical data
 Ichill 200CX EVO  rev 1.1  14/11/2013 
Pag. 98 of 151 
 ACF6  
•  The number of compressor of the 2 circuits (CF04 + CF05) is: 
√  > 4 
√  > 4 with no direct compressor start-up (CO10 ≠ 0) or the number of steps 
is > 0 (CF06), 
√  > 2 and the intermittent valve is configurated 
•  Pump-down function but at least in one circuit: 
√  The pump-down solenoid relay is not present 
√  No pump-down pressure switch or evaporating probe when 
  the pump-down is enabled with unit in start 
Or 
  No low pressure switch configurated. 
•  The compressor configuration with CF04 and CF05 but not the relay 
outputs: 
√  Main relay of the compressor 
√  Intermittent valve when enabled with the ON / OFF time (CO08 / CO09 
> 0) 
√  When the by-pass time >0 and there is no partialization or by-pass 
valve configured 
√  Coil 2 of part-winding start up 
√  Requested step valve for screw compressor are configurated 
•  One relay is configured as: 
√  Compressor not selected in CF04 or CF05 
√  Intermittent valve configured but CO08 =0 and CO09 =0 
√  By-pass gas valve configured but by-pass time = 0 
√  Coil 2 of part winding start up configured but direct start up selected 
• Wrong configuration of the capacity step valve 
ACF7 
Evaporator pump 
√  Enabled (CO16 >0) but the relay is not configured 
√  Not enabled (CO16>0) but the relay is configured 
Condenser pump 
√  Enabled (CO21 >0) but the relay is not configured 
√  Not enabled (CO21 = 0) but the relay is configured 
Allarm configuration water pump in antifizee alarm 
•  if Ar24=1 and Ar25=0 
or 
•  ifAr25=1 and not probe configurated like NTC 
•  if Ar29=1 and Ar30=0 
or 
• Ar29=1 and wrong confìguration of the probes 
ACF8 
• Regulation probe 
9  The regulation probe selected by ST09 or ST10 is not properly 
configured 
9  Compressor rack is configurated with termoregulation like pressure 
probe and the pressure probe is not configured 