Technical data

Ichill 200CX EVO rev 1.1 14/11/2013
Pag. 97 of 151
Label on alarm
visualization menu
ACF1
Heat pump unit selected but 4-way valve not configured
Wrong configuration of defrost parameters dF22 and dF23
ACF2
Condensing control enabled but condenser probes not configured
(one probe per circuit with 2 separate circuits, at least 1 probe for common
cond.)
Fan proportional control algorithm not respected:
FA09 + FA11 + FA12 < FA10
FA12 < FA13
FA07 < FA15 < FA08
Fan proportional control algorithm not respected and pump enabled:
FA18 + FA21 + FA20 < FA19
FA21 < FA22
FA16 < FA23 < FA17
Fan ON - OFF regulation algorithm not respected:
FA09 < FA10
Fan ON - OFF regulation algorithm not respected and pump enabled:
FA18 < FA19
If the defrost is enabled and no evaporating/condensing probes configured.
With triac regulation (CF68, CF69 = 2) the power supply configuration is
continuous control (CF63 = 2)
ACF3
Two relays, or two digital inputs, or two analog inputs are configured with
the same function or without the necessary resources (es. compressor 3
overload but compressor 3 relay not configured)
ACF4
CF59 = 1 and none digital input configured as Chiller request or Heat
Pump request
CF59 = 2 and none probe configured as external temperature probe
Unit configured as Heat pump and rack compressorr unit enabled (Cr010)
CF03 = 1 and wrong configuration of the digital input or digital output for
condensing unit unit
ACF5
Circuit # 2 not configured but at least one of its resources are present (e.g.:
solenoid
p
um
p
-down valve, heaters, inversion valve, fan, recover
y
, etc
)