Technical data
 Ichill 200CX EVO  rev 1.1  14/11/2013 
Pag. 97 of 151 
Label on alarm 
visualization menu
ACF1 
•  Heat pump unit selected but 4-way valve not configured 
•  Wrong configuration of defrost parameters dF22 and dF23 
ACF2 
•  Condensing control enabled but condenser probes not configured 
(one probe per circuit with 2 separate circuits, at least 1 probe for common 
cond.) 
•  Fan proportional control algorithm not respected: 
FA09 + FA11 + FA12 < FA10 
FA12 < FA13 
FA07 < FA15 < FA08 
•  Fan proportional control algorithm not respected and pump enabled: 
FA18 + FA21 + FA20 < FA19 
FA21 < FA22 
FA16 < FA23 < FA17 
•  Fan ON - OFF regulation algorithm not respected: 
FA09 < FA10 
•  Fan ON - OFF regulation algorithm not respected and pump enabled: 
FA18 < FA19 
•  If the defrost is enabled and no evaporating/condensing probes configured.
•  With triac regulation (CF68, CF69 = 2) the power supply configuration is 
continuous control (CF63 = 2) 
ACF3 
•  Two relays, or two digital inputs, or two analog inputs are configured with 
the same function or without the necessary resources (es. compressor 3 
overload but compressor 3 relay not configured) 
ACF4 
•  CF59 = 1 and none digital input configured as Chiller request or Heat 
Pump request 
•  CF59 = 2 and none probe configured as external temperature probe 
•  Unit configured as Heat pump and rack compressorr unit enabled (Cr01≠0)
•  CF03 = 1 and wrong configuration of the digital input or digital output for 
condensing unit unit 
ACF5 
Circuit # 2 not configured but at least one of its resources are present (e.g.: 
solenoid 
p
um
p
-down valve, heaters, inversion valve, fan, recover
y
, etc
)