Technical data
 Ichill 200CX EVO  rev 1.1  14/11/2013 
Pag. 95 of 151 
Symbol 
On the display the symbol 
 is blinking 
Action 
Alarm relay + buzzer ON 
Loads 
OFF 
AEE Eeprom alarm 
Label on alarm 
visualization menu 
AEE 
Origin 
Wrong eeprom data 
Reset 
------- 
Restart 
Manual 
Symbol 
On the display the symbol 
 is blinking 
Action 
Alarm relay + buzzer ON 
Loads 
OFF 
AFr: Power supply frequency alarm 
Label on alarm 
visualization menu 
AFr (Line frequency alarm) 
Origin 
Power supply frequency is not equal to the Par. CF63 
Reset  Ferquency control parameter adjusted, disabled CF63 = 2, frequency within 
the tolerance 
Restart 
Automatic 
Symbol 
On the display the symbol 
 is blinking 
Action 
Alarm relay + buzzer ON 
Loads 
OFF 
ALC1: Generic alarm with stop regulation 
Label on alarm 
visualization menu 
ALC1: generic alarm from digital input with stop regulation 
Origin 
Digital input configured as generic alarm with stop regulation active after the 
delay in Par. AL43 
Reset 
Digital input configured as generic alarm with stop regulation not active after 
the delay in Par. AL44 
Restart 
Automatic – It becomes manual after AL42 events/hour 
Logged only if manuale 
Symbol 
On the display the symbol 
 is blinking 
Action 
Alarm relay + buzzer ON 
REGULATION 
Alarm 
Alarm relay + buzzer ON 
Other loads 
OFF 
ATTENTION
If during AL44 the alarm stop and start again the AL44 time delay is reloaded. 
ALC2: Generic Signal alarm 
Label on alarm 
visualization menu 
ALC1: generic signal alarm from digital input if AL50 = 0 
Origin 
Digital input configured as generic alarm with stop regulation active after the 
delay in Par. AL52 
Reset 
Digital input configured as generic alarm with stop regulation not active after 
the delay in Par. AL53 
Restart 
Automatic 