Technical data

Ichill 200CX EVO rev 1.1 14/11/2013
Pag. 95 of 151
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer ON
Loads
OFF
AEE Eeprom alarm
Label on alarm
visualization menu
AEE
Origin
Wrong eeprom data
Reset
-------
Restart
Manual
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer ON
Loads
OFF
AFr: Power supply frequency alarm
Label on alarm
visualization menu
AFr (Line frequency alarm)
Origin
Power supply frequency is not equal to the Par. CF63
Reset Ferquency control parameter adjusted, disabled CF63 = 2, frequency within
the tolerance
Restart
Automatic
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer ON
Loads
OFF
ALC1: Generic alarm with stop regulation
Label on alarm
visualization menu
ALC1: generic alarm from digital input with stop regulation
Origin
Digital input configured as generic alarm with stop regulation active after the
delay in Par. AL43
Reset
Digital input configured as generic alarm with stop regulation not active after
the delay in Par. AL44
Restart
Automatic – It becomes manual after AL42 events/hour
Logged only if manuale
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer ON
REGULATION
Alarm
Alarm relay + buzzer ON
Other loads
OFF
ATTENTION
If during AL44 the alarm stop and start again the AL44 time delay is reloaded.
ALC2: Generic Signal alarm
Label on alarm
visualization menu
ALC1: generic signal alarm from digital input if AL50 = 0
Origin
Digital input configured as generic alarm with stop regulation active after the
delay in Par. AL52
Reset
Digital input configured as generic alarm with stop regulation not active after
the delay in Par. AL53
Restart
Automatic