Technical data

Ichill 200CX EVO rev 1.1 14/11/2013
Pag. 94 of 151
Origin
Active ID when it is configured as overload pump of evaporator 1
Active ID when it is configured as overload pump of support evaporator 2.
Reset
With active digital input
Restart
Manual (reset procedure in function menu).
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer ON
Loads
Evaporator water pump and compressors OFF
AtC1 - AtC2 Condenser pump overload alarm
Label on alarm
visualization menu
AtC1 (overload pump alarm of condenser 1)
AtC2 (overload pump alarm of support condenser 2)
Origin
Active ID when it is configured as overload pump of condenser 1
Active ID when it is configured as overload pump of condenser 2.
Reset
With active digital input
Restart
Manual (reset procedure in function menu).
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer ON
Loads
Condenser water pump and compressors OFF
AtAS Domestic hot water pump overload alarm
Label on alarm
visualization menu
AtAS (domestic hot water pump overload)
Origin
Digital input active
Reset
Digital input not active
Restart
Automatic reset if number of alarms per hour < AL75.
Manual reset if number of alarms per hour = AL75 (reset procedure in function
menu).
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer ON
Loads
Domestic hot water pump OFF
AtHS Sanitary heaters overload alarm
Label on alarm
visualization menu
AtHS (sanitary heaters overload)
Origin
Digital input active
Reset
Digital input not active
Restart
Manual (reset procedure in function menu)
Symbol
On the display the symbol
is blinking
Action
Alarm relay + buzzer ON
Loads
Sanitay heaters OFF
Phase sequence alarm
Label on alarm
visualization menu
ALSF
Origin
Digital input active
Reset
Digital input not active
Restart
Automatic