Technical data
 Ichill 200CX EVO  rev 1.1  14/11/2013 
Pag. 94 of 151 
Origin 
Active ID when it is configured as overload pump of evaporator 1 
Active ID when it is configured as overload pump of support evaporator 2. 
Reset 
With active digital input 
Restart 
Manual (reset procedure in function menu). 
Symbol 
On the display the symbol 
 is blinking 
Action 
Alarm relay + buzzer ON 
Loads 
Evaporator water pump and compressors OFF 
AtC1 - AtC2 Condenser pump overload alarm 
Label on alarm 
visualization menu 
AtC1 (overload pump alarm of condenser 1)  
AtC2 (overload pump alarm of support condenser 2) 
Origin 
Active ID when it is configured as overload pump of condenser 1 
Active ID when it is configured as overload pump of condenser 2. 
Reset 
With active digital input 
Restart 
Manual (reset procedure in function menu). 
Symbol 
On the display the symbol 
 is blinking 
Action 
Alarm relay + buzzer ON 
Loads 
Condenser water pump and compressors OFF 
AtAS Domestic hot water pump overload alarm 
Label on alarm 
visualization menu 
AtAS (domestic hot water pump overload) 
Origin 
Digital input active 
Reset 
Digital input not active 
Restart 
Automatic reset if number of alarms per hour < AL75. 
Manual reset if number of alarms per hour = AL75 (reset procedure in function 
menu). 
Symbol 
On the display the symbol 
 is blinking 
Action 
Alarm relay + buzzer ON 
Loads 
Domestic hot water pump OFF 
AtHS Sanitary heaters overload alarm 
Label on alarm 
visualization menu 
AtHS (sanitary heaters overload) 
Origin 
Digital input active 
Reset 
Digital input not active 
Restart 
Manual (reset procedure in function menu) 
Symbol 
On the display the symbol 
 is blinking 
Action 
Alarm relay + buzzer ON 
Loads 
Sanitay heaters OFF 
Phase sequence alarm 
Label on alarm 
visualization menu 
ALSF 
Origin 
Digital input active 
Reset 
Digital input not active 
Restart 
Automatic 