Technical data
 Ichill 200CX EVO  rev 1.1  14/11/2013 
Pag. 93 of 151 
Action 
Alarm Relay + and buzzer on only during normal running conditions. 
Loads 
OFF 
APFL: solar panel flow alarm 
Label on alarm 
visualization menu 
APFL solar panel flow alarm 
Origin 
The flow switch alarm is not detecded for AL69 seconds starting from water 
pump activation. 
Flow switch alarm is signalled if the digital input is active for AL71 seconds. 
Reset 
Automatic reset: digital input not active for AL72 seconds. 
Manual reset: Reset procedure in Menu function 
Type of alarm 
Automatic if flow switch digital input activation < AL70 + AL71 
Manual if Automatic if flow switch digital input activation > AL70 + AL71 
Symbol 
On the display the symbol 
 is blinking 
Action 
Alarm Relay + and buzzer on only during normal running conditions. 
Loads 
Solar panel water pump OFF 
AHFL: domestic hot water flow alarm 
Label on alarm 
visualization menu 
AHFL domestic hot water flow alarm 
Origin 
The flow switch alarm is not detecded for AL65 seconds starting from water 
pump activation. 
Flow switch alarm is signalled if the digital input is active for AL67 seconds. 
Reset 
Automatic reset: digital input not active for AL68 seconds. 
Manual reset: Reset procedure in Menu function 
Type of alarm 
Automatic if flow switch digital input activation < AL66 + AL67 
Manual if Automatic if flow switch digital input activation > AL66 + AL67 
Symbol 
On the display the symbol 
 is blinking 
Action 
Alarm Relay + and buzzer on only during normal running conditions. 
Loads 
Domestic hot water pump OFF 
AtSF: supply fan overload alarm 
Label on alarm 
visualization menu 
AtSF: Overload alarm of the supply fan 
Origin 
CF01=0: After on fan when the ID is activated for AL15 time. After on pump 
when the ID is activated for AL17. 
Reset 
Digital input not active for AL18 time 
Restart  Automatic – Manual if the digital input is active for AL16 seconds (Reset 
procedure in Menu function). 
Symbol 
On the display the symbol 
 is blinking 
Action 
Alarm relay + buzzer ON 
Loads 
OFF 
MANUAL RESET OF THE OVERLOAD ALARM OF THE SUPPLY FAN 
If the digital input is active for AL16 seconds it is necessary to restart manually the unit (reset procedure in 
larm Menu with blinking label Reset if the alarm is not active from Al18 otherwise label Active (can not be 
reset)). Push SET key to reset the alarm, the label disappears, the fan restarts and the alarm is by-passed 
for AL15 time delay to allow the start-up if within this interval the alarm does not appear again. 
AtE1 - AtE2 Evaporator pump overload alarm 
Label on alarm 
visualization menu 
AtE1 (overload pump alarm of evaporator 1)  
AtE2 (overload pump alarm of support evaporator 2) 