Technical data
 Ichill 200CX EVO  rev 1.1  14/11/2013 
Pag. 74 of 151 
If dF01=2, it determines the maximum duration of the defrost and even if, for the other cases, the end 
defrost condition are still to be satisfied. 
dF06 defrost delay time between the 1
st
 and the 2
nd
 circuit. 
After the interval dF09 determined by the defrost request of one of the circuits the other 2
nd
 circuits must wait 
also the time dF06 before defrosting. 
dF07 Compressor off time before the defrost (the led of the compressor is blinking) 
After the dF09 delay and before activating the defrost, the compressors are stopped for the dF07 time. 
Exactly in the middle of the dF07 time the 4-way valve is activated to equalise the pressure of the unit and when dF07 is completely 
expired the compressors and the defrost can start. 
This procedure does not respect the compressor on delay protection therefore the compressor is 
immediately turned off and then on. If dF07 = 0 the compressor is not stopped and the 4-way valve is 
immediately turned. 
dF08 Compressor off time after the defrost (the led of the compressor is blinking) 
After the defrost cycle the compressors are stopped for the dF08 time. 
Exactly in the middle of the dF07 time the 4-way valve is activated to equalise the pressure of the unit and to 
drain the external exchange unit, when dF08 is completely expired the unit restart in heat pump mode. 
This procedure does not respect the compressor on delay protection therefore the compressor is 
immediately turned off and then on. If dF08 = 0 the compressor is not stopped and the 4-way valve is 
immediately turned. 
DF09 Delay time to next defrost 
It starts when the condensing/evaporating temperature/pressure probe value is lower than dF02 setpoint. 
This time is reloaded if the power supply fails, after a defrost cycle or from a digital input request of defrost. 
The time counting is interrupted if the compressor is turned off or if the temperature/pressure is higher then 
dF02. 
dF10 Temperature setpoint to start a combined defrost of the circuit #1. 
It allows to set a temperature value to determines the beginning of a combined defrost. 
After the dF09 counting the NTC probe of the combined defrost of the circuit #1 is compared to the dF10 
setpoint, if the value is lower the defrost starts otherwise the unit runs in heat pump mode and when the 
temperature decreases under dF10 the defrost immediately starts. 
dF11 Temperature setpoint to end a combined defrost of the circuit #1. 
It allows to set a temperature value to determine the end of a combined defrost. 
When the NTC probe of the combined defrost of the circuit #1 becomes higher than dF10 setpoint the defrost 
cycle stops. 
dF12 Temperature setpoint to start a combined defrost of the circuit #2. 
It allows to set a temperature value to determine the beginning of a combined defrost. 
After the dF09 counting the NTC probe of the combined defrost of the circuit #2 is compared to the dF12 
setpoint, if the value is lower the defrost starts otherwise the unit runs in heat pump mode and when the 
temperature decreases under dF12 the defrost immediately starts. 
dF13 Temperature setpoint to end a combined defrost of the circuit #2. 
It allows to set a temperature value to determine the end of a combined defrost. 
When the NTC probe of the combined defrost of the circuit #2 becomes higher than dF13 setpoint the defrost cycle stops. 
dF14 All the resources on during the defrost of the circuit #1 
0= Not enabled 
1= Enabled 
dF15 All the resources on during the defrost of the circuit #2 
0= Not enabled 
1= Enabled 
dF16 Compressor step delay time in defrost. 
dF17 Condensing fan control during defrost and dripping cycle 
0= Not enabled 
1 = Enabled in defrost 
2= Enabled in defrost and in dripping time 
If dF17 = 0: During the defrost the fan control is not active. 
If dF17 = 1: when the condensing temperature/pressure value increases over dF18 the fans are turned on. 
the fan control is determined by the same algorithm used in chiller mode. 
If dF17 = 2: during the dripping time (dF08 <>0) the fan are turned on for the time duration set in dF08 . 
dF18 Pressure / temperature setpoint to force the fans on during the defrost 
When the temperature/pressure rises over this value the fan are turned on at the maximum speed. 
dF19 Time delay before starting a forced defrost 
It determines a delay time before starting the defrost cycle 
dF20 Temperature / pressure setpoint to force a defrost 