Technical data
 Ichill 200CX EVO  rev 1.1  14/11/2013 
Pag. 73 of 151 
Parameter dF23=0 dF23=1 dF23=2 
dF22=0  YES  not possible (ACF1)  not possible (ACF1) 
dF22=1 YES YES YES 
dF22=2  not possible (ACF1)  YES  not possible (ACF1) 
ATTENTION:
The configuration error ACF1 is displayed if the parameter value of dF22 and dF23 is not permitted. 
For only one condensing unit the dF22 and dF23 values must be not equal to 0. 
39.7  Defrost With Condenser Fan Procedure 
DEFROST WITH CONDENSER FANS 
If dF01 = 4 defrost is activated only through the condenser fans. 
If the temperature detected by the probe configured as external air temperature > dF26, instead of reverse 
the cycle, the compressor is stopped and is activated the condenser fan. 
The defrost ends: 
•  If the combined defrost is ON, for temperature or max time 
•  If only NTC probes are configured, for temperature or max time 
•  If only pressure probes are configured, for max time 
ATTENTION: 
also if the defrost through condenser fan is activated, if the external temperature < dF26, the defrost is 
through hot gas (compressor ON). 
If dF17 = 2 during dripping time (dF08 if different from 0) the ventilation is forced for the time set on dF08 
only if the temperature detected by the probe configured as external temperature is > of the Par. dF26 value. 
ATTENTION: 
With defrost with only ventilation enabled the forced defrost is always with hot gas. 
39.8  Defrost Parameter Description 
ATTENTION IT IS NOT POSSIBLE TO DO MODIFY THE dF PARAMETERS WHEN THE DEROST 
CYCLE IS RUNNING. 
dF01 Defrost mode 
0 = Defrost not enabled; 
1 = Temperature/pressure defrost. The dF09 “Time delay to defrost” starts to decrease when the 
temperature/pressure decreases under the dF02 setpoint. 
The defrost ends when pressure/temperature reaches the end defrost temperature/pressure. 
2 = Time duration defrost. The dF09, time delay to the defrost, starts when the temperature decreases under 
the dF02 setpoint (see start probe par. dF24). The defrost cycle ends after dF05 minutes. 
3 = Defrost starts when the temperature/pressure decreases under the dF02 setpoint (see start probe par. 
dF24) and stops when the digital input configured as “digital input to start defrost” is active. The delay dF09 
“Time delay to defrost” starts when the temperature decreases under the dF02 set point. The Defrost cycle 
ends when the digital input is active. 
4 = Defrost with condenser fan 
5= Defrost starts if the digital input configured as “digital input to start defrost” is active and ends when 
pressure/temperature reaches the end defrost temperature/pressure. 
dF02 Temperature / pressure to begin the time counting to next defrost. 
It allows to program a setpoint under which the dF09 starts counting. 
dF03 Temperature / pressure to end the defrost. 
It allows to program a temperature/pressure setpoint  value to determines the end of the defrost when the 
probe value is rising. 
dF04 Minimum duration of the defrost 
It determines the minimum defrost time duration after starting the defrost itself even if the conditions are not 
more satisfied. 
dF05 Maximum duration of the defrost 