Technical data
 Ichill 200CX EVO  rev 1.1  14/11/2013 
Pag. 72 of 151 
39.3 Forced Defrost  
The function is enabled if the parameter dF19>0. It allows to make a forced defrost cycle even if the dF09 
timeout counting is not expired, when the condensing/evaporating temperature/pressure is lower than dF20 
setpoint for the dF19 time counting. 
If during the dF19 time counting the condensing/evaporating temperature/pressure rises above the value 
dF20+dF21 (set+differential) the function is disabled and the tF19 time is reloaded. 
ATTENTION
: the forced defrost is not related to the dF09 /dF06 delay times, therefore the forced defrost cycle, if condition are OK, is 
immediately executed.
39.4 Combined Defrost 
The function is enabled if one of the digital input is configured as NTC temperature for combined defrost of 
the 1st or 2nd circuit. This probe detects the external air temperature of the condenser (evaporator in heat 
pump) and its temperature value determines the start and the stop of the defrost cycle. 
Description: 
The defrost count-down starts when the temperature/pressure of the probe, configured as 
condensing/evaporating circuit 1 or 2 probe, is lower than dF02 parameter. 
After the dF09 counting the instruments checks the temperature probe value (configured as combined 
defrost circuit 1 or 2) and if it is lower than dF10 (temperature setpoint to start the defrost of the circuit 1) or 
dF12 (temperature setpoint to start the defrost of the circuit 2) the defrost cycle starts, otherwise the unit still 
runs in heat pump mode. 
When the temperature decreases under the dF10 or dF12 values the defrost immediately start. 
The defrost ends when the NTC combined defrost probe 1 or 2 increases over dF11 (circuit1) or dF13 
(circuit2). 
39.5 Manual Defrost 
The manual defrost key function is enabled if the unit is on with at least one compressor running. 
The defrost start temperature/pressure of the controlled probe must be lower than dF02 setpoint value while 
if the combined defrost is active the detected temperature must be lower than dF10 or dF12. 
At this point by pushing 
 key in the “Defrost status of the circuit” visualization, the defrost starts. 
ATTENTION:
 the manual defrost is not related to the dF09 /dF06 delay times, therefore the forced defrost 
cycle, if condition are OK, is immediately executed for both circuits.
39.6  Defrost In Unit With Two Circuits 
39.6.1  Start defrost in unit with common condenser 
Parameter involved: dF22 
0= Independent 
1= Only if both circuit conditions are satisfied 
2= At least one circuit condition is satisfied 
39.6.2  End defrost in unit with two condenser 
Parameter involved: dF23 
0= Independent 
1= Both circuits have reached the conditions to stop the defrost 
2= At least one circuit has reached the end defrost condition 
Common condensation: possibile configuration 
Parametri dF23=0 dF23=1 dF23=2 
dF22=0  not possible (ACF1)  not possible (ACF1)  not possible (ACF1) 
dF22=1  not possible (ACF1)  YES  YES 
dF22=2  not possible (ACF1)  YES  not possible (ACF1) 
Separate condensation: possibile configuration 