Technical data
Ichill 200CX EVO rev 1.1 14/11/2013
Pag. 69 of 151
US 22
Auxiliary proportional output n° 1 operating mode
0= Not enabled
1= Always available with direct action
2= Available only when the unit is on with direct action
3= Always available with reverse action
4= Available only when the unit is on with reverse action
0 4
US 23
Analogue input configuration for auxiliary control 1
Allows to select which probe value Pb1..Pb10 controls output
1 10
US 24
Analog output 1 summer minimum set point
-30.0
-22
0.0
0
US26
°C
°F
Bar
Psi
Dec
int
Dec
int
US 25
Analog output 1 summer maximum set point
US26
70.0
158
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
US 26
Analog output 1 summer set point
US24 US25
°C
°F
Bar
Psi
Dec
int
Dec
int
US 27
Analog output 1 winter minimum set point
-30.0
-22
0.0
0
US29
°C
°F
Bar
Psi
Dec
int
Dec
int
US 28
Analog output 1 winter maximum set point
US29
70.0
158
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
US 29
Analog output 1 winter set point
US27 US28
°C
°F
Bar
Psi
Dec
int
Dec
int
US 30
Analog output 1 summer differential
0.0
0
0.0
0
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
US 31
Analog output 1 winter differential
0.0
0
0.0
0
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
US 32
Analog output 1 minimum value 0 US33 %
US 33
Analog output 1 maximum value US32 100 %
US 34
Auxiliary proportional output n° 2 operating mode
0= Not enabled
1= Always available with direct action
2= Available only when the unit is on with direct action
3= Always available with reverse action
4= Available only when the unit is on with reverse action
0 4
US 35
Analogue input configuration for auxiliary 2 control
Allows to select which probe value Pb1..Pb10 controls output
1 10