Technical data

Ichill 200CX EVO rev 1.1 14/11/2013
Pag. 64 of 151
MONDAY
X = 3 - Y= 7: the energy saving is enabled in time band 1 and time band 2, the automatic on is enabled in
time band 1, time band 2 and time band 3.
WEEKLY PROGRAMMING
Repeat the daily programming for the other days of the week using parameters ES08..ES13.
How to switch on the controller when it is off by real time clock
When the unit is in OFF by RTC and the parameter ES18 > 0, if the user switch on the controller by
keyboard the unit stay on for ES18 time; when this time is elapsed the unit return to OFF.
36. DYNAMIC SETPOINT
This function allows to modify the set point according to outside temperature or a 4..20mA analog input.
This function is enabled if:
In chiller mode the parameter Sd01 is not equal to 0.
In heat pump mode the parameter Sd02 is not equal to 0.
A analog input is configured as 4÷20mA for dynamic setpoint control or outside temperature
Dynamic setpoint diagram
Analog input configured as 4..20mA for dynamic setpoint: