Technical data
 Ichill 200CX EVO  rev 1.1  14/11/2013 
Pag. 59 of 151 
33.3  Condensing Unit: Common Or Separate Condenser 
FA05 defines the condenser unit 
Par. FA05 type of condenser 
FA05=0 Common condenser unit (only one common fan but a probe for each condenser is needed) 
FA05=1 Separate condenser units (one fan and one probe for circuit are needed) 
If FA05= 0 the condenser fan of the circuit 1 and circuit 2 works in parallel: 
•  CHILLER mode: the regulation probe is the probe that has the higher value  
•  HEAT PUMP mode: the regulation probe is the probe that has the lower value 
33.4  Proportional Regulation Of Condenser Fans 
Condenser fan in Chiller mode. 
Condenser fan in Heat pump mode. 
33.5  On/Off Regulation Of Condenser Fans 
Condenser fan in Chiller mode. 