29.1 Condenser Pump Group
It is possible to configure two condenser water pumps; the water pump to be activated is the pump with less
working hours.
When a water pump works continuosly for CO24 time, the other one is switched on and after CO25 second
the first one is switched off.
If a water pump overload occurs, the water pump is switched off and the other one is switched on.
30. CYCLIC OPERATION OF THE WATER PUMPS
If the water pump is OFF (reached set point), is possible to enable it to run to detect the right water
temperature.
At the end of the ON time, the controller verify if is necessary to switch on the compressor/s or not; if is not
necessary, the water pump is switched OFF for CO85 time and then switched on for another CO87 ON
cycle.
Parameters Description min max
unit of
measure
CO 85 Evaporator water pump OFF time if the set point is reached 0 250 10 min
CO 86 Evaporator water pump OFF time if the machine is STD-BY or
OFF
0 250 10 hour
CO 87 Evaporator water pump ON time 0 250 10 Sec
CO 88 Condenser water pump OFF time if the set point is reached 0 250 10 min
CO 89 Condenser water pump OFF time if the machine is STD-BY or
OFF
0 250 10 hour
CO 90 Condenser water pump ON time 0 250 10 Sec
31. HOT START
In the air air unit and in heating mode it is possible to stop the supply fan when the outlet evaporator
temperature falls below FA24 degrees.
FA24 Hot start Setpoint
FA25 Hot start differential