Technical data
 Ichill 200CX EVO  rev 1.1  14/11/2013 
Pag. 56 of 151 
29.1  Condenser Pump Group 
It is possible to configure two condenser water pumps; the water pump to be activated is the pump with less 
working hours. 
When a water pump works continuosly for CO24 time, the other one is switched on and after CO25 second 
the first one is switched off. 
If a water pump overload occurs, the water pump is switched off and the other one is switched on. 
30.  CYCLIC OPERATION OF THE WATER PUMPS 
If the water pump is OFF (reached set point), is possible to enable it to run to detect the right water 
temperature. 
At the end of the ON time, the controller verify if is necessary to switch on the compressor/s or not; if is not 
necessary, the water pump is switched OFF for CO85 time and then switched on for another CO87 ON 
cycle. 
Parameters  Description min max 
unit of 
measure 
CO 85  Evaporator water pump OFF time if the set point is reached  0  250  10 min 
CO 86  Evaporator water pump OFF time if the machine is STD-BY or 
OFF 
0 250 10 hour 
CO 87  Evaporator water pump ON time  0  250  10 Sec 
CO 88  Condenser water pump OFF time if the set point is reached  0  250  10 min 
CO 89  Condenser water pump OFF time if the machine is STD-BY or 
OFF 
0 250 10 hour 
CO 90  Condenser water pump ON time  0  250  10 Sec 
31. HOT START 
In the air air unit and in heating mode it is possible to stop the supply fan when the outlet evaporator 
temperature falls below FA24 degrees. 
FA24 Hot start Setpoint 
FA25 Hot start differential 










