Technical data
 Ichill 200CX EVO  rev 1.1  14/11/2013 
Pag. 54 of 151 
28.2 Modulating Evaporator Water Pump 
To enable the modulating evaporator water pump is necessary to configure an analog output as “Modulated 
evaporator water pump” (see analog and digital output configuration) . 
The modulating evaporator water pump is enabled in cooling, heating and sanitary hot water production; if 
the machine is in STD-BY or OFF the water pump is OFF. 
The water pump works according the Dt between two probes, which can be choosen both in summer an 
winter mode, among those configured in the instrument (Pb1, Pb2,…). 
If the state of the water pump is tied to the state of the compressor, when last compressor is switched off the 
water pump is forced to run at US60 speed for CO18 minutes, then it is switched off. 
If the state of the water pump is not tied to the state of the compressor, when last compressor is switched off 
the water pump is forced to run at US60 speed. 
The regulation is done as showed below. 
Chiller and chiller + sanitary hot water (machine with valves OUt1 and OUT2 in the gas circuit) 
Parameter Description  min max udm   
US 47  Probe 1 selection for evaporator water pump modulation in chiller  0  10     
US 48  Probe 2 selection for evaporator water pump modulation in chiller  0  10     
US 49  Set point for maximum speed of modulationg evaporator water pump in chiller  30.0 
-58 
0.0 
0 
70.0 
158 
50.0 
725 
°C 
°F 
Bar 
Psi 
Dec 
int 
Dec 
int 
US 50  Proportional band for maximum speed of modulationg evaporator water pump 
in chiller 
0.0 
0 
0.0 
0 
25.0 
45 
14.0 
203 
°C 
°F 
Bar 
Psi 
Dec 
int 
Dec 
int 
US 51  Minimum speed of the evaporator water pump in chiller  0  100  %   
US 52  Maximum speed of the evaporator water pump in chiller  0  100  %   
Heat pump and domestic hot water 