Technical data
 Ichill 200CX EVO  rev 1.1  14/11/2013 
Pag. 52 of 151 
26.2 Condenser High Pressure, Condenser High Temperature Or Evaporator Low 
Pressure 
UNLOADING ACTIVATION IN CHILLER MODE 
When the condenser pressure or temperature is higher than CO44 the unit works with the number of 
compressors selected in CO49 parameter or CO96 speed in case of inverter compressor. 
If the compressor is a screw compressor the unloading function works at least CO50 time; if CO50 = 0 this 
function is disabled. 
EXAMPLE
2 circuits and 3 compressors per circuit 
6 compressors are running; if CO49 = 2 in case of unloading 2 compressors are switched off and 4 
continuous to work. 
UNLOADING DE-ACTIVATION IN CHILLER MODE 
When the condenser pressure or condenser temperature falls below CO44-CO45 the unloading function is 
disabled and all compressor are available to work. 
Other information about the Unloading in chiller 
If the condenser pressure or condenser temperature remains between CO44 and CO44-CO45, after CO48 
time the unloading function is deactivated. 
UNLOADING IN HEAT PUMP MODE 
The reference probe for this function is the evaporator probe; if any evaporator probe is configured, the 
function uses the condenser probe.  
When the evaporator/condenser pressure is lower than CO46 the unit works with the number of compressors 
selected in CO49 parameter or CO96 speed in case of inverter compressor. 
If the compressor is a screw compressor the unloading function works at least CO50 time; if CO50 = 0 this 
function is disabled. 
EXAMPLE
2 circuits and 3 compressors per circuit 
6 compressors are running; if CO49 = 2 in case of unloading 2 compressors are switched off and 4 
continuous to work. 
UNLOADING DE-ACTIVATION in HEAT PUMP MODE 
When the evaporator probe (orcondenser pressure or condenser temperature) increase over CO46+CO47 
the unloading function is disabled and all compressor are available to work. 
Other information about the Unloading in Heat Pump 
If the evaporator probe (or condenser pressure or condenser temperature) remains between CO46 and 
CO46+CO47, after CO48 time the unloading function is deactivated. 
26.3  Low Temperature Of The Evaporator Water Outlet 
ACTIVATION 
The lower value between the inlet evaporator probe, common outlet evaporator probe or outlet probe for the 
circuit, enables the unloading function. 
When the value of one of the probes above decrease under the set point CO55 the unloading function is 
activated; the number of active compressors/step is determined by the CO49 parameter or CO96 speed in 
case of inverter compressor. 
The display shows the label b1EU – b2EU alternated to a default visualization. 
DE-ACTIVATION 