Technical data
 Ichill 200CX EVO  rev 1.1  14/11/2013 
Pag. 50 of 151 
Low pressure alarm (when the low pressure switch is used) is disabled for AL02 time after valve activation 
(AL02=0 the alarm is disabled when the compressor is OFF). 
When first compressor of the circuit is switched on, the solenoid valve is switched on 1 seconds before it. 
CO36 = 2 Pump down enabled during the switching off and switching on (low pressure switch or 
pump down switch) 
Compressor switching off: 
before turning off the last compressor, the solenoid valve is closed; the compressor works until the pressure 
switch is activated or after a maximum time CO39; in this case an alarm is displayed (b1PH or b2PH) but the 
machine continuous to work as normal. 
If the alarm occurs more than AL21 times per hour, the Ichill generate a manual alarm. 
Low pressure alarm (when the low pressure switch is used) is disabled for AL02 time after valve activation 
(AL02=0 the alarm is disabled when the compressor is OFF). 
Compressor switching on: 
when first compressor of the circuit is switched on, the solenoid valve is switched on 1 seconds before it. 
If the pump down pressure switch remains active, the compressors does not restart and after CO39 time a 
pump-down alarm is displayed. 
The parameter AL23 allows to choose if the pump down alarm (during the switching on) is automatic or 
manual reset: 
  AL23 =0 automatic reset; the compressor will rester when the pump down pressure switch is active 
  AL23=1 manual reset; if the number of pump down alarm per hour is lower than AL22 the reset is 
automatic, manual reset; if the number of pump down alarm per hour is higher than AL22 the reset is 
manual 
PAR. CO36 = 3 Pump down enabled during the switching off only in chiller mode (low pressure 
switch or pump down switch) 
The pump douwn procedure works as CO36=1 but only in chiller mode; in heat pump mode the solenoid 
valve is activated when the first compressor is ON and de-activated when the last compressor is OFF. 
PAR. CO36 = 4 Pump down enabled during the switching off and switching on inly in chiller mode 
(low pressure switch or pump down switch) 
The pump douwn procedure works as CO36=2 but only in chiller mode; in heat pump mode the solenoid 
valve is activated when the first compressor is ON and de-activated when the last compressor is OFF. 
PUMP DOWN with low pressure probe 
CO36 = 1 Pump down enabled during the switching off (low pressure probe) 
Before turning off the last compressor, the solenoid valve is closed; the compressor works until the pressure 
falls below CO37 or after a maximum time CO39; in this case an alarm is displayed (b1PH or b2PH) but the 
machine continuous to work as normal. 
If the alarm occurs more than AL21 times per hour, the Ichill generate a manual alarm. 
Low pressure alarm (when the low pressure switch is used) is disabled for AL02 time after valve activation 
(AL02=0 the alarm is disabled when the compressor is OFF). 
When the first compressor of the circuit is switched on, the solenoid valve is switched on 1 seconds before it. 
CO35 = 2 Pump down enabled during the switching off and switching on (low pressure probe) 
Before turning off the last compressor, the solenoid valve is closed; the compressor works until the pressure 
falls below CO37 or after a maximum time CO39; in this case an alarm is displayed (b1PH or b2PH) but the 
machine continuous to work as normal. 
If the alarm occurs more than AL21 times per hour, the Ichill generate a manual alarm. 
Low pressure alarm (when the low pressure switch is used) is disabled for AL02 time after valve activation 
(AL02=0 the alarm is disabled when the compressor is OFF). 
When the first compressor of the circuit is switched on, the solenoid valve is switched on 1 seconds before it 
and the compressor is switched on if the pressure is higher than CO37 + CO38. 
If the pressure remains lower than CO37 + CO38 the compressors does not restart and after CO39 time a 
pump-down alarm is displayed. 
The parameter AL23 allows to choose if the pump down alarm (during the switching on) is automatic or 
manual reset: 
  AL23 =0 automatic reset; the compressor will rester when the pump down pressure switch is active 