Technical data
 Ichill 200CX EVO  rev 1.1  14/11/2013 
Pag. 48 of 151 
CO81 
Maximum speed of the inverter compressors in sanitary water 
1 100 
% 
CO82 
Outside temperature to reduce inverter compressor speed in 
Heat pump 
-
50.0 
-58 
0.0 
0 
70.0 
158 
50.0 
725 
°C 
°F 
Bar 
Psi 
Dec 
int 
Dec 
int 
CO83 
Hysteresis temperature to reduce inverter compressor speed in 
Heat pump 
0.1 
0 
0.1 
1 
25.0 
45 
14.0 
203 
°C 
°F 
Bar 
Psi 
Dec 
int 
Dec 
int 
CO84 
Compressor speed if outside temperature > CO82  0  100  %   
21.1  Inverter Compressor In Heat Pump And External Temperature 
It is possible to reduce the compressor speed (both compressor in parallel if configured) in heat pump when 
external temperature increases over a determined temperature. 
22. COMPRESSOR RACK 
The Ichill can manage a compressor rack: 
•  the machine must have only one gas circuit 
•  the machine must work only in cooling mode (machine only chiller) 
•  the machine has to regulate in proportional mode 
•  the machine must have max. ON/OFF compressors 
The parameter Cr01 allows to enable the compressor rack regulation: 
Cr01 = 0  Compressor rack regulation disabled 
Cr01 = 1  Compressor rack enabled and regulation on the probe defined by parameter ST09 
Cr01 = 2  Compressor rack enabled and regulation on the evaporator trasducer (that has to be 
configured) 
It is possible to choose the number of compressors the controller can use in case of regulation faulty probe; 
the parameter involved is Cr08. 
It is possible to choose the number of condenser fan steps the controller can use in case of faulty probe; the 
parameter involved is Cr09. 
The Energy Saving function, in case of compressor rack unit, has dedicated set point and differential 
(parameter Cr06 = “Energy saving offset for compressor rack unit”, Cr07 = “Energy saving differential for 
compressor rack unit”) 