Technical data
 Ichill 200CX EVO  rev 1.1  14/11/2013 
Pag. 47 of 151 
Parameters involved: 
CO60 
Operation time at CO61 power when the compressor inverter 
controlled is switched on 
0 250 sec 
CO61 
Forced power when the compressor inverter controlled is 
switched on 
0 100  % 
CO62 
Delay to increase the power during the start up phase of the 
compressori inverter controlled 
1 250 
sec 
CO63 
Compressor inverter controlled operation power under whitch 
start counting CO64 time 
0 100  % 
CO64 
Maximun operation time of the compressor inverter controlled 
with power less than CO63 
0 250 Min 
10 Min 
CO65 
Operating time of the compressor inverter controlled at 
maximum power 
0 250 sec 
10sec 
CO66 
Maximum operating time of the compressor inverter controlled 
0 999  Hr  1Hr 
CO67 
Minimum value of the compressor 1 inverter controlled 
0 CO68 
% 
CO68 
Maximum value of the compressor 1 inverter controlled 
CO67 100 
% 
CO69 
Minimum value of the compressor 2 inverter controlled 
0 CO70 
% 
CO70 
Maximum value of the compressor 2 inverter controlled 
CO69 100 
% 
CO71 
Delay to increase/decrease the power of the compressori 
inverter controlled 
1 250 
sec 
... 
CO79 
Maximum speed of the inverter compressors in chiller 
1 100 
% 
CO80 
Maximum speed of the inverter compressors in heat pump 
1 100 
% 










