Technical data

Ichill 200CX EVO rev 1.1 14/11/2013
Pag. 47 of 151
Parameters involved:
CO60
Operation time at CO61 power when the compressor inverter
controlled is switched on
0 250 sec
CO61
Forced power when the compressor inverter controlled is
switched on
0 100 %
CO62
Delay to increase the power during the start up phase of the
compressori inverter controlled
1 250
sec
CO63
Compressor inverter controlled operation power under whitch
start counting CO64 time
0 100 %
CO64
Maximun operation time of the compressor inverter controlled
with power less than CO63
0 250 Min
10 Min
CO65
Operating time of the compressor inverter controlled at
maximum power
0 250 sec
10sec
CO66
Maximum operating time of the compressor inverter controlled
0 999 Hr 1Hr
CO67
Minimum value of the compressor 1 inverter controlled
0 CO68
%
CO68
Maximum value of the compressor 1 inverter controlled
CO67 100
%
CO69
Minimum value of the compressor 2 inverter controlled
0 CO70
%
CO70
Maximum value of the compressor 2 inverter controlled
CO69 100
%
CO71
Delay to increase/decrease the power of the compressori
inverter controlled
1 250
sec
...
CO79
Maximum speed of the inverter compressors in chiller
1 100
%
CO80
Maximum speed of the inverter compressors in heat pump
1 100
%