Technical data
 Ichill 200CX EVO  rev 1.1  14/11/2013 
Pag. 44 of 151 
Compressor Cap. 
step 1 
Cap. 
step 
2 
Cap. 
step 3 
 Power 
    0 % 
    25 % 
    50 % 
       75 % 
       100 % 
ATTENTION
When working with capacity control in sequential step in direct or reverse modes: if the power requested is 
50% and 75% the unit turn on also the step 25% that must be enabled to make run the other two. 
20.1  Minimum Load Start- Up 
Par. CO07: configuration of the start-up with minimum load. 
This parameter allows to configure the first capacity step operation mode for alternative compressors and 
screw compressors. 
CO07=0 
First capacity step is used only to start the compressor at the minimum load; the valve is switched on for 
CO13 seconds, then it is switche off. 
CO07=1 
First capacity step is used as lower step of the regulation. 
CO07=2 SCREW COMPRESSOR 
First capacity step is used only to start the screw compressor at the minimum load; the valve is ON when the 
compressor is OFF and it remains ON for CO13 seconds after the switching ON of the compressor. 
CO07=3 SCREW COMPRESSOR 
First capacity step is used as lower step of the regulation; when the compresor is OFF the valve is ON. 
20.2  INTERMITTENT SOLENOID VALVE FOR SCREW COMPRESSOR 
Some screw compressors have an intermittent solenoid valve; when the compressor is ON, this valve stays 
CO08 ON and CO09 OFF. 
21.  COMPRESSOR INVERTER CONTROLLED 
The signal 0÷10V is given by one of 4 configurable outputs of the Ichill (OUT1÷OUT4). 
The compressor inverter controlled can be used only with proportional regulation (parameter St11=0). 
Possible unit configuration: 
•  1 circuit: 1 compressor inverter controlled 
•  1 circuit: 1 compressor inverter controlled and maximum 2 ON/OFF compressor (managed by relay) 
•  2 circuits: 1 compressor inverter controlled per circuit 
•  2 circuits: 1 compressor inverter controlled and maximum 2 ON/OFF compressor (managed by 
relay) per circuit 
First step to be activated is always the compressor inverter controlled; it will be swiched on when the 
regulation requests 100% of the compressor power. 
To increase / decrease the power the compressor works by step of 1% of the power; every step is delayed 
by CO62 at the start-up of the compressor and CO71 when the compressor works normally. 
When the compressor inverter controlled is activated, it works at power configured by CO61 parameter for 
CO60 seconds; after that: 
•  if the parameter CO62=0 the compressor modulates the power according to the regulation request 