Technical data
 Ichill 200CX EVO  rev 1.1  14/11/2013 
Pag. 32 of 151 
20 Temperature probe NTC for combined defrost circuit 1 
21 Temperature probe NTC for free cooling water inlet 2 
22 Temperature probe NTC for auxiliary output 1 
23 Temperature probe NTC for auxiliary output 2 
24 Temperature probe NTC sanitary water 1 
25 Temperature probe NTC sanitary water 2 
26 Temperature probe NTC solar panel 
27  Condenser probe circuit 1 ( temperature NTC / pressure 4÷20 mA / ratio-metric 0÷ 5Volt ) 
28  Condenser probe circuit 2 ( temperature NTC / pressure 4÷20 mA / ratio-metric 0÷ 5Volt ) 
29  Evaporator pressure probe circuit 1 (pressure 4÷20 mA / ratio-metric 0÷ 5Volt ) 
30  Evaporator pressure probe circuit 1 (pressure 4÷20 mA / ratio-metric 0÷ 5Volt ) 
31  Aux 1 output probe control  (4÷20 mA / ratio-metric 0÷ 5Volt) 
32  Aux 2 output probe control  (4÷20 mA / ratio-metric 0÷ 5Volt) 
33  Dynamic setpoint probe (4÷20 mA) 
34  Compressor 1 or circuit 1 pressure probe 
35  Compressor 2 or circuit 2 pressure probe 
After the number 35 the display read-out goes from “o 1” to “c75 that allows to set an analogue input as 
digital input (see polarity input of digital inputs). 
Digital Input Configuration Id1 – Id11 
0. Not enabled 
1.  Remote ON / OFF 
2.  Remote chiller / heat pump 
3.  Flow switch/ Supply fan overload 
4.  Flow switch of heated side 
5.  Antifreeze heater circuit 1 
6.  Antifreeze heater circuit 2 
7.  High pressure switch circuit 1 
8.  High pressure switch circuit 2 
9.  Low pressure switch circuit 1 
10.  Low pressure switch circuit 2 
11.  Compressor 1 high pressure 
12.  Compressor 2 high pressure 
13.  Compressor 3 high pressure 
14.  Compressor 4 high pressure 
15. Not used 
16. Not used 
17. Compressor 1 overload 
18. Compressor 2 overload 
19. Compressor 3 overload 
20. Compressor 4 overload 
21. Not used 
22.  Condenser fan overload of circuit 1 
23.  Condenser fan overload of circuit 2 
24.  Condenser fan overload of circuit 1 and 2 (comun) 
25.  Water pump overload of evaporator 1 
26.  Water support pump overload of evaporator 
27.  Water pump overload of condenser 1 
28.  Water support pump overload of condenser 
29.  Recovery request circuit 1 
30.  Recovery request circuit 2 
31.  Start/End defrost circuit 1 
32.  Start/End defrost circuit 2 
33. Energy Saving 
34.  Pressure switch / compressor 1 oil 
35.  Pressure switch / compressor 2 oil 
36.  Pressure switch / compressor 3 oil 
37.  Pressure switch / compressor 4 oil 
38. Not used 
39. Not used 
40.  Pump down pressure switch of circuit 1 
41.  Pump down pressure switch of circuit 2 