Technical data

Ichill 200CX EVO rev 1.1 14/11/2013
Pag. 25 of 151
Pou4 Proportional output for dumper control or to drive the external relay 4
ICX207D outputs (I/O expansion):
PoE1 Proportional output for dumper control or to drive the external relay 1
PoE2 Proportional output for dumper control or to drive the external relay 2
PoE3 Proportional output for dumper control or to drive the external relay 3
The labels are displayed only if the corresponding output is present and configured.
TO SEE THE FOUR OUTPUT PERCENTAGE:
Enter the function menu
1. Use the UP or DOWN keys to select Pout.
2. Push SET key: the bottom display shows Pou1, the top display shows the output percentage.
3. Use the UP or DOWN keys to select Pou1, Pou2, Pou3, etc. the top display always shows the value,
between 0% and 100%, of the proportional output of the selected circuit.
4. To exit the Hour function push MENU key or wait the timeout.
ATTENTION:
If the proportional output Pou1 - Pou2 - Pou3 - Pou4 are configured to drive an external relay the
display will show 0=relay off and 100=relay on
.
Read-out of the time counting to the next defrost
dF FUNCTION
Label involved in dF function:
dF1 delay time to next defrost of the circuit 1
dF2 delay time to next defrost of the circuit 2
Enter the function menu :
1. Use the UP or DOWN keys to select dF
2. Push SET key: the dF1 label is showed on the top display, the bottom display shows the time delay to
next defrost in minutes / seconds. The
icon is on.
3. Use the UP or DOWN keys to select dF1 or dF2.
4. To exit the Hour function push MENU key or wait the timeout
Read-out of the probes configured to control Solar panel
Sol FUNCTION
Label involved in Sol function:
FCP1 Free cooling probe 1 temperature
FCP2 Free cooling probe 2 temperature
FCdF Free cooling differential
FCrL Free cooling water pump status
FCAn Free cooling analog output status
Read-out of the probes configured to control Free cooling
Sol FUNCTION
Label involved in Sol function:
SLPb Solar panel probe 1 temperature
SSP2 Solar panel probe 2 temperature
SSdi Solar panel differential
SPMP Solar panel water pump status
SLrL Solar panel valve status
Read-out of the probes configured to control an auxiliary output relay
uS FUNCTION.
Label involved in uS function:
uSt1 auxiliary probe value of the circuit 1
uSt2 auxiliary probe value of the circuit 2
Enter the function menu
1. Use the UP or DOWN keys to select uS.