Technical data
 Ichill 200CX EVO  rev 1.1  14/11/2013 
Pag. 24 of 151 
The running hours is displayed on the top display, the resolution is x 10 hours (eg 2 means 20 hours, 20 
means 200hours) 
Enter the function Menu 
1.  Use the UP or DOWN keys to select Hour 
2.  Push SET key: bottom display = above labels, top display = hours x10. The time 
 is on. 
3.  Use the UP or DOWN keys to scroll the list. 
4.  To exit the Hour function push MENU key or wait the timeout 
Reset the running hour 
Enter the function Menu 
1.  Within the Hour function select, with UP or DOWN, the interested label: CO1H, CO2H, CO3H, CO4H,  
EP1H, EP2H, CP1H, CP2H, SAPH, PAPH or FCPH. 
2. Push the SET keys for 3 seconds: the top display shows the running hours blinking value, then it shows 
0 to confirm the reset. The next load label is automatically loaded. 
To exit the Hour function push MENU key or wait the timeout 
Read-out of the compressor starts-up 
For each compressor is possible to show the number of starts-up. 
COSn FUNCTION. 
Label involved in COSn function: C1S number of compressor 1 starts-up .. C4S number of compressor 4 
starts-up 
The labels are displayed only if the corresponding output is present and configured 
The number of starts-up is displayed on the top display, the resolution is x 10 (eg 2 means 20 starts, 20 
means 200 starts) 
Enter the function Menu 
1.  Use the UP or DOWN keys to select COSn. 
2. Push SET one time: the label of the first load C1S is showed on the top display, the bottom display 
shows the number x10. 
3.  With UP or DOWN scroll the compressor list. 
4.  To exit the Hour function push MENU key or wait the timeout 
 Reset the starts-up number 
Enter the function Menu 
1.  Within the Hour function select, with UP or DOWN, the interested label: CS1, CS2, CS3, CS4. 
2. Push the SET keys for 3 seconds: the top display shows the running hours blinking value, then it shows 
0 to confirm the reset. The next load label is automatically loaded. 
3.  To exit the Hour function push MENU key or wait the timeout. 
Read-out of the Proportional Output percentage of the condenser fan control 
The proportional outputs of the two circuits, that control the fan speed, can be showed in the menu function. 
Cond FUNCTION. 
Label involved in Cond function. 
Cnd1 output value of the condenser fan of the circuit 1. 
Cnd2 output value of the condenser fan of the circuit 2. 
TO SEE THE OUTPUT PERCENTAGE: 
Enter the function menu 
1.  Use the UP or DOWN keys to select Cond. 
2. Push  SET key: the bottom display shows Cnd1, the top display shows the output percentage. 
3.  Use the UP or DOWN keys to select Cnd1 or Cnd2, the top display always shows the value, between 
0% and 100%, of the proportional output of the selected circuit. 
4.  To exit the Hour function push MENU key or wait the timeout. 
Read-out of the proportional output value (outputs OUT1...OUT4) 
The four proportional outputs, 4..20ma or 0-10V, can be showed in the menu function. 
Pout FUNCTION selects the proportional outputs. 
Label involved in Pout function: 
IC200CX outputs: 
Pou1 Proportional output for dumper control or to drive the external relay 1 
Pou2 Proportional output for dumper control or to drive the external relay 2 
Pou3 Proportional output for dumper control or to drive the external relay 3 