Technical data

Ichill 200CX EVO rev 1.1 14/11/2013
Pag. 23 of 151
THE ALARM LIST CONTAINS 100 EVENTS IN A FIFO STRUCTURE. WHEN THE MEMORY IS FULL
ANY NEW ALARM WILL ERASE THE OLDEST.
Disable – enable a circuit
CrEn FUNCTION.
Label involved with CrEn function: Cr1E = circuit 1, Cr2E = circuit 2
DISABLE A CIRCUIT
Enter the function Menu
1. Use UP or DOWN keys to select CrEn on the bottom display
2. Push SET key: the bottom display Cr1E, top display En.
3. Select the circuit 1 or 2 with UP or DOWN (Cr1E or Cr2E).
4. Push SET key for 3 seconds when one of the two Cr1E, Cr2E label are displayed. The top display shows
the En blinking label, use the UP or DOWN to change in diS (Disabled) or En (Enabled). Then push SET
key to confirm the new selection. The display shows next circuit status.
5. To exit the CrEn function push MENU key or wait the timeout.
Read-out of a Circuit Not enabled
If one circuit is disabled the bottom display shows diS alternated with the label name of the measurement
selected.
Circuit 1 = diS the bottom display shows b1dS = circuit 1 disabled.
Circuit 2 = diS the bottom display shows b2dS = circuit 2 disabled.
Enable or disable a single compressor
COEn FUNCTION
Label involved in COEn function: CO1E = Compressor 1 status… CO4E = Compressor 4 status
The COEn function uses only the compressors configured by the corresponding output parameters.
Enter the function Menu
1. Use the UP or DOWN keys to select COEn.
2. Push SET key: bottom display = CO1E, top display = En
3. Select the compressor with UP or DOWN: CO2E - CO3E - CO4E if available.
4. Push SET for 3 seconds when the label corresponds to the compressor to disable: CO1E - CO2E -
CO3E - CO4E. Top display shows the blinking En label, use the UP or DOWN key and change to diS
(Compressor disabled) or En (compressor enabled) then push SET to confirm, the display shows next
item.
5. To exit the COEn function push MENU key or wait the timeout.
Read-out of the compressor discharge temperature probe
The menu function allows to read-out the compressor temperature probes.
COdt FUNCTION.
Label involved in Codt function: CO1t Compressor 1 discharge temperature… CO4t Compressor 4
discharge temperature
1. Use the UP or DOWN keys to select COdt
2. Push SET key: bottom display = CO1t, top display = temperature value of that probe.
3. Use the UP or DOWN kys to scroll the list: CO1t or CO2t or CO3t or CO4t
4. To exit the COEn function push MENU key or wait the timeout
Read-out of the running hours
This menu allows to shows all the time running hours of the compressors, supply fan and pumps.
Hour FUNCTION to show the controlled load consumption
Label involved in the Hour function:
CO1H Compressor 1 running hours .. CO4H Compressor 6 running hours.
EP1H Evaporator water pump or Supply fan running hours
EP2H Support evaporator water pump running hours
CP1H Condenser water pump running hours
CP2H Support condenser water pump running hours
SAPH Domestic hot water pump
running hours
PAPH Solar panel water pump
running hours
FCPH Free cooling water pump running hours
The labels are displayed only if the corresponding output is present and configured.