Technical data
 Ichill 200CX EVO  rev 1.1  14/11/2013 
Pag. 23 of 151 
THE ALARM LIST CONTAINS 100 EVENTS IN A FIFO STRUCTURE. WHEN THE MEMORY IS FULL 
ANY NEW ALARM WILL ERASE THE OLDEST. 
Disable – enable a circuit 
CrEn FUNCTION. 
Label involved with CrEn function: Cr1E = circuit 1, Cr2E = circuit 2 
DISABLE A CIRCUIT 
Enter the function Menu 
1. Use UP or DOWN keys to select CrEn on the bottom display 
2. Push SET key: the bottom display Cr1E, top display En. 
3.  Select the circuit 1 or 2 with UP or DOWN (Cr1E or Cr2E). 
4. Push SET key for 3 seconds when one of the two Cr1E, Cr2E label are displayed. The top display shows 
the En blinking label, use the UP or DOWN to change in diS (Disabled) or En (Enabled). Then push SET 
key to confirm the new selection. The display shows next circuit status. 
5.  To exit the CrEn function push MENU key or wait the timeout. 
Read-out of a Circuit Not enabled 
If one circuit is disabled the bottom display shows diS alternated with the label name of the measurement 
selected. 
Circuit 1 = diS the bottom display shows b1dS = circuit 1 disabled. 
Circuit 2 = diS the bottom display shows b2dS = circuit 2 disabled. 
Enable or disable a single compressor 
COEn FUNCTION 
Label involved in COEn function: CO1E = Compressor 1 status… CO4E = Compressor 4 status 
The COEn function uses only the compressors configured by the corresponding output parameters. 
Enter the function Menu 
1. Use the UP or DOWN keys to select COEn. 
2.  Push SET key: bottom display = CO1E, top display = En 
3.  Select the compressor with UP or DOWN: CO2E - CO3E - CO4E if available. 
4.  Push SET for 3 seconds when the label corresponds to the compressor to disable: CO1E - CO2E - 
CO3E - CO4E. Top display shows the blinking En label, use the UP or DOWN key and change to diS 
(Compressor disabled) or En (compressor enabled) then push SET to confirm, the display shows next 
item. 
5.  To exit the COEn function push MENU key or wait the timeout. 
Read-out of the compressor discharge temperature probe 
The menu function allows to read-out the compressor temperature probes. 
COdt FUNCTION. 
Label involved in Codt function: CO1t Compressor 1 discharge temperature… CO4t Compressor 4 
discharge temperature 
1. Use the UP or DOWN keys to select COdt 
2.  Push SET key: bottom display = CO1t, top display = temperature value of that probe. 
3.  Use the UP or DOWN kys to scroll the list: CO1t or CO2t or CO3t or CO4t 
4.  To exit the COEn function push MENU key or wait the timeout 
Read-out of the running hours 
This menu allows to shows all the time running hours of the compressors, supply fan and pumps. 
Hour FUNCTION to show the controlled load consumption 
Label involved in the Hour function: 
CO1H Compressor 1 running hours .. CO4H Compressor 6 running hours. 
EP1H Evaporator water pump or Supply fan running hours 
EP2H Support evaporator water pump running hours 
CP1H Condenser water pump running hours 
CP2H Support condenser water pump running hours 
SAPH Domestic hot water pump 
running hours  
PAPH Solar panel water pump 
running hours  
FCPH Free cooling water pump running hours  
The labels are displayed only if the corresponding output is present and configured. 