Technical data

Ichill 200CX EVO rev 1.1 14/11/2013
Pag. 20 of 151
Fig.2: upper display shows outlet 2 evaporator temperature, the lower display shows Out2.
Pressing SET key is possible to read the same probe of the first circuit.
Fig.2
9. DISPLAY INFORMATION
Read Set Point value
Push and release the SET key, the leds of the circuits are off and the set value is displayed.
In stand-by the bottom display shows SetC (set chiller), by pushing SET again the next label is SetH (set
heat pump ).
If the unit is running the only set displayed is related to the running mode.
Modify the Set Point
1) Push SET key for at least 3 seconds: the leds of the circuits are off and the set value is blinking.
2) Use the UP or DOWN key to modify the setpoint.
3) Push SET to confirm or wait the timeout (15seconds).
Read real SetPoint during Energy Saving or Dynamic Setpoint
Chiller mode: push SET one time, the bottom display shows the SEtC (set chiller) while the top display
shows the set value. Only if the Energy saving or the Dynamic Setpoint are active, pushing another time the
SET key, the bottom display shows “SEtr” (real setpoint), and the top display shows the setpoint that the
unit is really using for the thermoregulation.
Chiller mode: push SET one time, the bottom display shows the SEtH (set Heat pump) while the top display
shows the set value. Only if the Energy saving or the Dynamic Setpoint are active, pushing another time the
SET key, the bottom display shows “SEtr” (real setpoint), and the top diplay shows the setpoint that the unit
is really using for the thermoregulation.
ATTENTION
The SEtr label appears only if the Energy saving or the Dynamic Setpoint are active.