Letter can be: 
o (open) = function associated to the input or output is active when the contact is open 
c (close) = function associated to the input or output is active when the contact is closed 
The number defines the function associated to the input or output. 
Example 1: 
The bottom display shows the parameter label CF36 = digital input 7 configuration: 
•  7 means that the digital input is configured as “high pressure switch of circuit 1” (see digital input 
configuration) 
•  o means that the digital input is active for open contact, then the high pressure alarm is detected 
when the digital input is open. 
Example 2: 
The bottom display shows the parameter label CF36 = digital input 7 configuration: 
•  7 means that the digital input is configured as “high pressure switch of circuit 1” (see digital input 
configuration) 
•  c means that the digital input is active for closed contact, then the high pressure alarm is detected 
when the digital input is closed. 
8. DISPLAY LAYOUT 
Pushing   or   key it is possible to read the valure of the probes connected to the instrument. 
Every probe is identified by a label (see display visualization table). 
Example: 
Fig.1: upper display shows outlet 1 evaporator temperature, the lower display shows Out1. 
Pressing SET key is possible to read the same probe of the second circuit (if configured). 
Fig.1 