Technical data
 Ichill 200CX EVO  rev 1.1  14/11/2013 
Pag. 18 of 151 
1.  Enter Pr3 level 
2.  Select a whatever parameter family 
3. Search “Pr3” label; push SET key to change the value that now is blinking. 
4.  Use UP or DOWN key to insert the NEW PASSWORD value, then push SET to confirm the new value. 
5.  The top display blinks for some seconds and then shows the next parameter 
6.  Exit the programming pushing SET + UP together or wait the timeout. 
Inside the Pr3 level it is possible to change also the Pr1 and Pr2 passwords. 
Move a parameter level from Pr2 to Pr1 
Enter Pr2 programming level 
Select the parameter and if the led # 3 is off: the parameter is available only in Pr2. 
To show the parameter also in Pr1:
1.  Keep pushed SET key; 
2.  Push 1 time the DOWN key and the led 3 should be on, the parameter is now available in Pr1. 
To hide the parameter in Pr1:
1.  Keep pushed SET key; 
2.  Push 1 time the DOWN key and the led 3 should be off, the parameter is now removed from Pr1. 
Move a parameter from Pr3 to Pr2 to Pr1 
Enter Pr3 programming level, here the parameter are all visible: 
Select the parameter, if all the leds are off the parameter is available only in Pr3. 
To show the parameter also in Pr2 and Pr1:
1.  Keep pushed SET key; 
2.  Push 1 time the DOWN key and the leds 3 and 4 should be on, the parameter is now available also in 
Pr2 / Pr1. 
To show the parameter only in Pr2:
1.  Keep pushed SET key; 
2.  Push 1 time the DOWN key and the leds 3 is off, the parameter is now available also in Pr2. 
To show the parameter only in Pr3:
1.  Keep pushed SET key 
2.  Push 1 time the DOWN key and the leds 3 and 4 are off, the parameter is now available only in Pr3. 
Visibility and Parameter value locked 
To set the only visibility and lock the parameter value it is necessary enter Pr3 programming level. 
Pr1 PARAMETER VISIBILITY 
Enter the Pr3 level 
1.  Select the parameter; 
2.  Keep pushed the SET key; 
3.  Push 1 time the MENU key and the led 3 change from on to blinking: the parameter is visible in Pr1 but 
can’t be changed. 
Pr2 PARAMETER VISIBILITY 
Enter the Pr3 level 
1.  Select the parameter; 
2.  Keep pushed the SET key; 
3.  Push 1 time the MENU key and the led 4 change from on to blinking the parameter is visible in Pr2 but 
can’t be changed. 
Leds 3 / 4 blinking:  the parameter is visible in Pr1 and in Pr2 but in those levels now they can’t be 
changed. 
TO SET THE ORIGINAL TAG FOR THE PARAMETER Pr1 / Pr2 
1.  Keep pushed the SET key; 
2.  Push one time the MENU key, the leds 3 / 4 turn on, the parameter can be seen and modified in Pr1 and Pr2. 
Programming: digital input and output polarity 
The configuration parameters of : 
• Digital inputs 
•  Digital outputs (relay) 
•  Proportional output configured as ON/OFF 
•  Analogue input configured as digital input 
are composed by a letter and a number. 










