Technical data
 Ichill 200CX EVO  rev 1.1  14/11/2013 
Pag. 151 of 151 
55.5  RT314 KIT 
Relay module (DIN rail mounting) 
55.6  HOT KEY: 
Parameters copying key 
56. TECHNICAL DATA 
Housing: self extinguishing ABS 
Case: frontal 32x74 mm; depth 60mm 
Mounting: panel mounting in a 29x71mm panel cut-out 
Frontal protection: IP65 
Display: 
Top Display 4 digits with d.p. 
 Bottom Display 4 digits with d.p. 
Power supply: 
12Vac -10% ÷ +15% 50/60 Hz or 
 24 Vac/dc ±10% 50/60 Hz 
Power absorption: 10VA max. 
Analog Inputs: 4 configurable (NTC/PTC/digital input) + 2 configurable (NTC/PTC/4÷20ma/0÷5Volt/digital 
input) 
Digital inputs: 11 (free voltage) 
Relay outputs: IC206CX: 6 SPDT 5(2) A, 250Vac, IC208CX: 8 SPDT 5(2) A, 250Vac 
Max. current on common line: 10A 
Data storing: on the non-volatile memory (EEPROM). 
Operating temperature: -10÷55 °C 
Storage temperature: -30÷85 °C 
Relative humidity: 20÷85% (no condensing) 
Measuring range: - 50÷110 °C (- 58 ÷ 230 °F) NTC / -50.0÷150 °C (-58÷302 °F) PTC or 0÷ 50 bar (0÷725 
psi) 
Resolution: 0,1 °C or 1 °F 
Accuracy of the controller at 25°C: ±0,7 °C ±1 digit 