Technical data

Ichill 200CX EVO rev 1.1 14/11/2013
Pag. 146 of 151
52.5 XJ485CX CONNECTION
The XJ485CX interface is a signal converter (from TTL to RS485). The RS485 uses two terminals (+) and (-)
that must be connected respecting the polarity. Use the CAB/RS02 to connect the XJ485 interface to the TTL
connector.
52.6 REMOTE KEYBOARD VI620CX
It is possible to connect max. 2 VI620CX remote keyboards:
set the dip switch of the keyboard 1 to “1” position and enable remote keybord 1 (parameter CF54)
set the dip switch of the keyboard 2 to “ON” position and enable remote keybord 2 (parameter CF55)
A shielded cable has to be used for the connection up to 150 mt maximum.
In case of communication failure the upper display shows “noL” (no link).
Use the CAB/CJ30 to interface the ichill connector to the shielded cable.
52.1 I/O EXPANSION MODULE CONNECTION