Technical data

Ichill 200CX EVO rev 1.1 14/11/2013
Pag. 140 of 151
51.2 HARDWARE RESOURCES FOR 208CX MODELS
8 digital outputs (relays): MAX current on the relay contacts relè 5(2)A 250V - MAX common
current 10A 250V
11 digital inputs: (free of voltage)
analogue inputs:
4 NTC / PTC probes
2 NTC / PTC / pressure transducer 4÷20 mA / pressure transducer ratio-metric 0÷ 5.0 Volt
4 modulating outputs:
2 configurable 0 ÷ 10 Volt
2 configurable 0 ÷ 10.0 Volt or PWM (for modulating condenser fan)
1 output to connect a remote keyboard (max 2 remote keyboards)
1 LAN to connect an i-o expansion module (ICX207D)
1 TTL output for “hot key 64” or for XJ485CX (interface module for monitoring system)
51.3 ANALOG INPUTS NTC – PTC PROBES
PbC = common terminal
Pb1…Pb6 = probe inputs