Technical data
 Ichill 200CX EVO  rev 1.1  14/11/2013 
Pag. 139 of 151 
50. BLACK-OUT 
After the black-out is restored: 
1.  The instrument resores the same operating mode lost after the supply failure. 
2.  If active, the defrost is aborted. 
3.  All the timers and time parameters are reloaded. 
4.  The manual alarm is not reset. 
51. WIRING CONNECTIONS 
51.1 HARDWARE RESOURCES FOR IC206CX MODEL 
•  6 digital outputs (relays):   MAX current on the relay contacts relè 5(2)A 250V - MAX common 
current 10A 250V 
•  11 digital inputs:   (free of voltage) 
•  analogue inputs: 
•  4 NTC / PTC probes 
•  2 NTC / PTC / pressure transducer 4÷20 mA / pressure transducer ratio-metric 0÷ 5.0 Volt 
•  4 modulating outputs: 
•  2 configurable 0 ÷ 10 Volt 
•  2 configurable 0 ÷ 10.0 Volt or PWM (for modulating condenser fan) 
•  1 output to connect a remote keyboard (max 2 remote keyboards) 
•  1 LAN to connect an i-o expansion module (ICX207D) 
•  1 TTL output for “hot key 64” or for XJ485CX (interface module for monitoring system) 










