Technical data

Ichill 200CX EVO rev 1.1 14/11/2013
Pag. 138 of 151
AL59 Maximum number of high water temperature alarm events
Always manual reset if AL59 = 0
Always automatic reset if AL59 =16
From automatic to manual reset if AL59 =1..15
0 16
AL60 High water temperature alarm delay time from ON compressor 0 250 sec 10 sec
AL61 Set point higt water temperature -50.0
-58
110
230
°C
°F
Dec
int
AL62 Differential higt water temperature 0.1
0
25.0
45
°C
°F
Dec
int
AL63 Analogue input configuration.Allows to select which probe value NTC/PTC
(Pb1..Pb10)
0 20
AL64 Low pressure alarm delay 0 250 sec
AL65 Sanitary water flow switch alarm delay 0 250 Sec
AL66 San. water flow switch delay to stop pump 0 250 Sec
AL67 Sanitary water flow switch activation time 0 250 Sec
AL68 San. water flow switch de-activation time 0 250 Sec
AL69 Solar panel flow switch alarm delay 0 250 Sec
AL70 Solar panel flow switch delay to stop pump 0 250 Sec
AL71 Solar panel flow switch activation time 0 250 Sec
AL72 Solar panel flow switch de-activation time 0 250 Sec
AL73 Max. number per hour sanitary water heaters overload alarm
Always manual if AL73 = 0
Always automatic if AL73 =16
If 16>AL73>0:
automatic if number of alarm < AL73
manual if number of alarm = AL73
0 16
AL74 Password request to reset manual antifreeze alarm
0= password requested
1= password not requested
0 1
AL75 Max. number per hour sanitary water pump overload
Always manual if AL75 = 0
Always automatic if AL75 =16
If 16>AL75>0:
automatic if number of alarm < AL75
manual if number of alarm = AL75
0 16
AL76 Compressor oil level alarm only signalling
0= automatic / manual reset oil alarm (see AL13) and compressor switch off
1= oil alarm signal only (compressor stays ON)
0 1
AL77 Compressor overload alarm operation mode
0= always manual reset
1= always automatic reset
0 1
AL78
Dt temperature to generate compressor/circuit differential oil alarm
0.1
1
14.0
203
bar
psi
Dec
int
AL79
Differential to reset compressor/circuit differential oil alarm
0.1
1
14.0
203
bar
psi
Dec
int
AL80 Max. number per hour compressor/circuit differential oil alarm
Always manual if AL80 = 0
Always automatic if AL80 =16
If 16>AL80>0:
automatic if number of alarm < AL80
manual if number of alarm = AL80
0 16
AL81 Compressor/circuit differential oil alarm operation mode
0= disabled
1= enabled for pistons compressors
2= enabled for screw compressors
0 2
AL82 By pass time of the FC flow switch alarm starting from water pump activation 0 250 Sec
AL83 FC flow switch time activation before blocking FC water pump 0 250 Sec
AL84 FC flow switch activation time to generate the alarm and block the compressor 0 250 Sec
AL85 FC flow switch de-activation time to reset the alarm 0 250 Sec
AL86 Flow switch alarm reset mode
0= Always manual
1= automatic reset after 1 minute
2= automatic reset after 2 minutes
...
250= automatic reset after 250 minutes
0 250 min
AL87 Evaporator/sanitary water flow switch by-pass time during Out1 / Out2
commutation
0 250 Sec