Technical data
 Ichill 200CX EVO  rev 1.1  14/11/2013 
Pag. 138 of 151 
AL59    Maximum number of high water temperature alarm events 
Always manual reset if AL59 = 0 
Always automatic reset if AL59 =16 
From automatic to manual reset if AL59 =1..15 
0 16     
AL60    High water temperature alarm delay time from ON compressor  0  250  sec  10 sec 
AL61    Set point higt water temperature  -50.0 
-58 
110 
230 
°C 
°F 
Dec 
int 
AL62    Differential higt water temperature  0.1 
0 
25.0 
45 
°C 
°F 
Dec 
int 
AL63    Analogue input configuration.Allows to select which probe value NTC/PTC 
(Pb1..Pb10) 
0 20 
AL64    Low pressure alarm delay  0  250  sec   
AL65    Sanitary water flow switch alarm delay  0  250  Sec   
AL66    San. water flow switch delay to stop pump  0  250  Sec   
AL67    Sanitary water flow switch activation time  0  250  Sec   
AL68    San. water flow switch de-activation time  0  250  Sec   
AL69    Solar panel flow switch alarm delay  0  250  Sec   
AL70    Solar panel flow switch delay to stop pump  0  250  Sec   
AL71    Solar panel flow switch activation time  0  250  Sec   
AL72    Solar panel flow switch de-activation time  0  250  Sec   
AL73    Max. number per hour sanitary water heaters overload alarm 
Always manual if AL73 = 0 
Always automatic if AL73 =16 
If 16>AL73>0: 
•  automatic if number of alarm < AL73 
•  manual if number of alarm = AL73 
0 16     
AL74    Password request to reset manual antifreeze alarm 
0= password requested 
1= password not requested 
0 1     
AL75    Max. number per hour sanitary water pump overload 
Always manual if AL75 = 0 
Always automatic if AL75 =16 
If 16>AL75>0: 
•  automatic if number of alarm < AL75 
•  manual if number of alarm = AL75 
0 16     
AL76    Compressor oil level alarm only signalling 
0= automatic / manual reset oil alarm (see AL13) and compressor switch off 
1= oil alarm signal only (compressor stays ON) 
0 1     
AL77    Compressor overload alarm operation mode 
0= always manual reset 
1= always automatic reset 
0 1     
AL78   
Dt temperature to generate compressor/circuit differential oil alarm 
0.1 
1 
14.0 
203 
bar 
psi 
Dec 
int 
AL79   
Differential to reset compressor/circuit differential oil alarm 
0.1 
1 
14.0 
203 
bar 
psi 
Dec 
int 
AL80    Max. number per hour compressor/circuit differential oil alarm 
Always manual if AL80 = 0 
Always automatic if AL80 =16 
If 16>AL80>0: 
•  automatic if number of alarm < AL80 
•  manual if number of alarm = AL80 
0 16     
AL81    Compressor/circuit differential oil alarm operation mode 
0= disabled 
1= enabled for pistons compressors 
2= enabled for screw compressors 
0 2     
AL82    By pass time of the FC flow switch alarm starting from water pump activation  0  250  Sec   
AL83    FC flow switch time activation before blocking FC water pump  0  250  Sec   
AL84    FC flow switch activation time to generate the alarm and block the compressor 0  250  Sec   
AL85    FC flow switch de-activation time to reset the alarm  0  250  Sec   
AL86  Flow switch alarm reset mode 
0= Always manual 
1= automatic reset after 1 minute 
2= automatic reset after 2 minutes 
... 
250= automatic reset after 250 minutes 
0 250 min   
AL87  Evaporator/sanitary water flow switch by-pass time during Out1 / Out2 
commutation 
0 250 Sec   