Technical data
 Ichill 200CX EVO  rev 1.1  14/11/2013 
Pag. 135 of 151 
FS 51   
Compressors safety time in sanitary water 
0= safety time enabled 
1= safety time disabled 
0 1     
FS 52   
Set point to enable heaters for low sanitary water temperature  -50.0 
-58 
110.0 
230 
°C 
°F 
FS 53   
Proportional band to enable heaters for low sanitary water temperature  0.1 
0 
25.0 
45 
°C 
°F 
FS 54   
Probe selection for low sanitary water temperature 
0= disabled 
1= Pb1 
2= Pb2 
... 
0 20     
FS 55   
Solar panel opration mode for sanitary water 
0= disabled 
1= integration to heat pump 
2= substitution to heat pump 
0 2     
FS 56   
Solar panel opration mode for heating 
0= disabled 
1= integration to heat pump 
2= substitution to heat pump 
0 2     
FS 57   
Probe selection to calculate Dt of solar panel in sanitary water 
0= disabled 
1= Pb1 
2= Pb2 
… 
0 20     
FS 58   
Probe selection to calculate Dt of solar panel in heating 
0= disabled 
1= Pb1 
2= Pb2 
… 
0 20     
FS 59   
Dt to enable solar panel in sanitary water  0.1 
0 
25.0 
45 
°C 
°F 
Dec 
int 
FS 60   
Dt to enable solar panel in heating  0.1 
0 
25.0 
45 
°C 
°F 
Dec 
int 
FS 61   
Maximum operation time of solar panel if set point not reached  0  250  min   
FS 62   
Probe selection to disable the Free cooling for low temperature 
0 20 
FS 63   
Set point to disable the Free cooling for low temperature  -50.0 
-58 
110.0 
230 
°C 
°F 
FS 64   
Differential to disable the Free cooling for low temperature  0.1 
0 
25.0 
45 
°C 
°F 
Parameter  Description  min  max  M. u.  Resolution 
AL 1   Low pressure alarm delay from analog and digital input  0  250  Sec   
AL 2   Low pressure alarm delay from digital input after compressor stop if the low 
pressure switch is used for the pump down. 
AL02= 0 low pressure alarm not enable with compressor OFF 
AL02≠ 0 low pressure alarm enable after AL02 time with compressor OFF 
0 250 10 Sec   
AL 3   Low pressure alarm setpoint from analogue input  -50.0 
-58 
0.0 
0 
110.0 
230 
50.0 
725 
°C 
°F 
bar 
psi 
Dec 
int 
Dec 
int 
AL 4   Low pressure alarm differential from analogue input  0.1 
0 
0.1 
1 
25.0 
45 
14.0 
203 
°C 
°F 
bar 
psi 
Dec 
int 
Dec 
Int 
AL 5   Maximum number of low pressure events from digital/analogue inputs: 
Manual reset if AL05 = 0 
Automatic reset if AL05 =16 
From automatic to manual reset if AL05= 1..15 
0 16     
AL 6   Low temperature/pressure alarm during defrost 
0= Not enabled 
1= Enabled 
0 1     
AL 7   Low temperature/pressure alarm delay during defrost  0  250  Sec   
AL 8   Low temperature/pressure alarm with unit in OFF or stand – by: 
0 = Not enabled 
1= Alarm enabled 
0 1     
AL 9   High temperature/pressure alarm from analogue input  -50.0 
-58 
0.0 
0 
110.0 
230 
50.0 
725 
°C 
°F 
bar 
psi 
Dec 
int 
Dec 
int 
AL 10    High temperature/pressure alarm differential from analogue input  0.1 
0 
0.1 
1 
25.0 
45 
14.0 
203 
°C 
°F 
bar 
psi 
Dec 
int 
Dec 
int 
AL 11    Low oil pressure / level delay from digital input  0  250  Sec   