Technical data

Ichill 200CX EVO rev 1.1 14/11/2013
Pag. 135 of 151
FS 51
Compressors safety time in sanitary water
0= safety time enabled
1= safety time disabled
0 1
FS 52
Set point to enable heaters for low sanitary water temperature -50.0
-58
110.0
230
°C
°F
FS 53
Proportional band to enable heaters for low sanitary water temperature 0.1
0
25.0
45
°C
°F
FS 54
Probe selection for low sanitary water temperature
0= disabled
1= Pb1
2= Pb2
...
0 20
FS 55
Solar panel opration mode for sanitary water
0= disabled
1= integration to heat pump
2= substitution to heat pump
0 2
FS 56
Solar panel opration mode for heating
0= disabled
1= integration to heat pump
2= substitution to heat pump
0 2
FS 57
Probe selection to calculate Dt of solar panel in sanitary water
0= disabled
1= Pb1
2= Pb2
0 20
FS 58
Probe selection to calculate Dt of solar panel in heating
0= disabled
1= Pb1
2= Pb2
0 20
FS 59
Dt to enable solar panel in sanitary water 0.1
0
25.0
45
°C
°F
Dec
int
FS 60
Dt to enable solar panel in heating 0.1
0
25.0
45
°C
°F
Dec
int
FS 61
Maximum operation time of solar panel if set point not reached 0 250 min
FS 62
Probe selection to disable the Free cooling for low temperature
0 20
FS 63
Set point to disable the Free cooling for low temperature -50.0
-58
110.0
230
°C
°F
FS 64
Differential to disable the Free cooling for low temperature 0.1
0
25.0
45
°C
°F
Parameter Description min max M. u. Resolution
AL 1 Low pressure alarm delay from analog and digital input 0 250 Sec
AL 2 Low pressure alarm delay from digital input after compressor stop if the low
pressure switch is used for the pump down.
AL02= 0 low pressure alarm not enable with compressor OFF
AL02 0 low pressure alarm enable after AL02 time with compressor OFF
0 250 10 Sec
AL 3 Low pressure alarm setpoint from analogue input -50.0
-58
0.0
0
110.0
230
50.0
725
°C
°F
bar
psi
Dec
int
Dec
int
AL 4 Low pressure alarm differential from analogue input 0.1
0
0.1
1
25.0
45
14.0
203
°C
°F
bar
psi
Dec
int
Dec
Int
AL 5 Maximum number of low pressure events from digital/analogue inputs:
Manual reset if AL05 = 0
Automatic reset if AL05 =16
From automatic to manual reset if AL05= 1..15
0 16
AL 6 Low temperature/pressure alarm during defrost
0= Not enabled
1= Enabled
0 1
AL 7 Low temperature/pressure alarm delay during defrost 0 250 Sec
AL 8 Low temperature/pressure alarm with unit in OFF or stand – by:
0 = Not enabled
1= Alarm enabled
0 1
AL 9 High temperature/pressure alarm from analogue input -50.0
-58
0.0
0
110.0
230
50.0
725
°C
°F
bar
psi
Dec
int
Dec
int
AL 10 High temperature/pressure alarm differential from analogue input 0.1
0
0.1
1
25.0
45
14.0
203
°C
°F
bar
psi
Dec
int
Dec
int
AL 11 Low oil pressure / level delay from digital input 0 250 Sec