Technical data
 Ichill 200CX EVO  rev 1.1  14/11/2013 
Pag. 134 of 151 
FS 15   
Minimum value of the Antilegionella set point 
-50.0 
-58 
FS14 
°C 
°F 
Dec 
int 
FS 16   
Maximum value of the Antilegionella set point 
FS14 
110.0 
230 
°C 
°F 
Dec 
int 
FS 17   
Hour selection for the Antilegionella activation 
0 24.00 Hr  10 min 
FS 18   
Day selection for the Antilegionella activation 
0 7     
FS 19   
Minimum operating working time of the Antilegionella cycle 
1 250 min   
FS 20   
Temperature band for heaters deactivation during Antilegionella cycle 
0.1 
0 
25.0 
45 
°C 
°F 
Dec 
int 
FS 21   
Temperature differential to enable the freecooling function 
0.1 
0 
25.0 
45 
°C 
°F 
Dec 
int 
FS 22   
Temperature differential for the free cooling regulation 
0.1 
0 
25.0 
45 
°C 
°F 
Dec 
int 
FS 23   
Set point for solar panel activation 
FS25 FS26 °C/°F  dec/int 
FS 24   
Differential value for solar panel deactivation 
0.1 
0 
25.0 
45 
°C 
°F 
Dec 
int 
FS 25   
Minimum value of the solar panel set point 
-50.0 
-58 
FS23 
°C 
°F 
Dec 
int 
FS 26   
Maximum value of the solar panel set point 
FS23 
110.0 
230 
°C 
°F 
Dec 
int 
FS 27   
Delay time to activate the sanitary water valve starting from pump activation 
0 250 sec   
FS 28   
Delay time to deactivate the sanitary water pump starting from valve 
deactivation 
0 250 sec   
FS 29   
Maximum operating working time of the Antilegionella cycle 
0 250 min   
FS 30   
Sanitary water: security set point 
-50.0 
-58 
110.0 
230 
°C 
°F 
FS 31   
Sanitary water: security differential 
0.1 
0 
25.0 
45 
°C 
°F 
FS 32   
Sanitary water: minimum interruption time 
0 250 min   
FS 33   
Sanitary water pump operation mode 
0 1     
FS 34   
Free cooling water pump OFF time if chiller only Free cooling 
0 250 min   
FS 35   
Free cooling water pump ON time if chiller only Free cooling 
0 250 sec   
FS 36   
Free cooling maximum time 
0 250 min   
FS 37   
Set point Free cooling  -50.0 
-58 
0.0 
0 
110.0 
230 
50.0 
725 
°C 
°F 
bar 
psi 
Dec 
int 
Dec 
int 
FS 38   
Proportional band Free coling  0.1 
0 
0.1 
1 
25.0 
45 
14.0 
203 
°C 
°F 
Bar 
Psi 
Dec 
int 
Dec 
int 
FS 39   
Minimum value Free cooling analog output 
0 100 %   
FS 40   
Maximum value Free cooling analog output 
0 100 %   
FS 41   
T1 probe selection for Free cooling 
0=disabled, 1=Pb1, 2=Pb2, etc. 
0 20     
FS 42   
T2 probe selection for Free cooling 
0=disabled, 1=Pb1, 2=Pb2, etc. 
0 20     
FS 43   
Outside temperature set point to force the maximum speed of condenser 
fan 
-50.0 
-58 
110.0 
230 
°C 
°F 
FS 44   
Outside temperature differential to force the maximum speed of condenser 
fan 
0.1 
0 
25.0 
45 
°C 
°F 
FS 45   
Delay time of condenser fan regulation during Free cooling 
0 250 min   
FS 46   
Antilegionella cycle opreration mode 
0= compressors and heaters 
1= compressors are first inserted and then heaters 
2= only heaters 
3= only compressors 
0 3     
FS 47   
Evaporator water pump enabled is Sanitary water 
0= enabled 
1= disabled 
0 1     
FS 48   
Probe selection to force exit from Sanitary water 
0= disabled 
1= probe Pb1 
2= probe Pb2 
... 
0 20     
FS 49   
Start production Sanitary water 
0= when all compressors are requested 
1= when at least one compressor is requested 
0 1     
FS 50   
Set point to force OFF the compressors during antilegionella cycle  -50.0 
-58 
110.0 
230 
°C 
°F 