Technical data

Ichill 200CX EVO rev 1.1 14/11/2013
Pag. 133 of 151
dF 33
Hybrid exchangers differential 1 in heat pump
0.1
0
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
dF 34
Hybrid exchangers differential 2 in heat pump
0.1
0
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
dF 35 Probe selection of the Hybrid exchangers
0= outside temperature
1= condenser temperature/pressure
0 1
dF 36 Forced time Hybrid exchangers in chiller mode when the compressor is
switched on
0 250 sec
dF 37
Max. offset of the Defrost dinamic set point
-30.0
-54
-14.0
-203
30.0
54
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
dF 38
Outside temperature set point of the Defrost dinamic set point
-50.0
-58
110.0
230
°C
°F
Dec
int
dF 39
Outside temperature differential of the Defrost dinamic set point
-30.0
-54
30.0
54
°C
°F
Dec
int
Parameter Description min max M. u. Resolution
rC 1 Sanitary water regulation mode 0 2
rC 2 Recovery modes
0 = not enabled
1 = 2 indipendent circuit
2 = both the circuit in parallel
0 250 Sec
rC 3 Delay time delay with step forced off 0 250 Sec
rC 4 Delay time delay with step forced off after the recovery valve activation 0 250 Min
rC 5 Recovery minimum time 0 250 Min
rC 6 Minimum interval time between the end and the beginning of the next
recovery
-50.0
-58
0.0
0
110.0
230
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
rC 7 Temperature setpoint to disable the recovery 0.1
0
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
rC 8 Temperature differential to restore the recovery 0 250 Min
rC 9 Maximum time with recovery disabled (if temperature/pressure within rC6-
rC7)
0 1
Parameter Description min max M. u. Resolution
FS 1
Sanitary water regulation mode
0= not enabled
1=valves in water circuit
2=valves in gas circuit
0 2
FS 2
Sanitary water thermoregulation priority
0 = heating / cooling
1 = sanitary water
2 = sanitary water by digital input
0 2
FS 3
Sanitary water thermoregulation set point
FS05 FS06 °C/°F dec/int
FS 4
Sanitary water thermoregulation band
0.1
0
25.0
45
°C
°F
Dec
int
FS 5
Minimum value of the sanitary water set point
-50.0
-58
FS06
°C
°F
Dec
int
FS 6
Maximum value of the sanitary water set point
FS05
110.0
230
°C
°F
Dec
int
FS 7
Full loads enabling to reach the sanitary water set point
0 1
FS 8
Heaters enabling during the sanitary water thermoregulation
0= not enabled
1= compressors + heaters
2= only heaters
3= only compressors
0 1
FS 9
Operation working time to activate the heaters during the sanitary water
thermoregulation
0 250 Min
FS 10
Time delay to activate the sanitary water valve
0 999 sec int
FS 11
Reversing cycle delay during sanitary water thermoregulation
0 999 sec int
FS 12
Antilegionella function operating mode
0 = interval time
1= weekly
2= daily
0 2
FS 13
Delay time between two Antilegionella cycles
0 250 Hr 0
FS 14
Antilegionella Set point
FS15 FS16 °C/°F dec/int