Technical data
 Ichill 200CX EVO  rev 1.1  14/11/2013 
Pag. 133 of 151 
dF 33   
Hybrid exchangers differential 1 in heat pump 
0.1 
0 
0.1 
1 
25.0 
45 
14.0 
203 
°C 
°F 
Bar 
Psi 
Dec 
int 
Dec 
int 
dF 34   
Hybrid exchangers differential 2 in heat pump 
0.1 
0 
0.1 
1 
25.0 
45 
14.0 
203 
°C 
°F 
Bar 
Psi 
Dec 
int 
Dec 
int 
dF 35    Probe selection of the Hybrid exchangers 
0= outside temperature 
1= condenser temperature/pressure 
0 1     
dF 36    Forced time Hybrid exchangers in chiller mode when the compressor is 
switched on 
0 250 sec   
dF 37   
Max. offset of the Defrost dinamic set point 
-30.0 
-54 
-14.0 
-203 
30.0 
54 
14.0 
203 
°C 
°F 
Bar 
Psi 
Dec 
int 
Dec 
int 
dF 38   
Outside temperature set point of the Defrost dinamic set point 
-50.0 
-58 
110.0 
230 
°C 
°F 
Dec 
int 
dF 39   
Outside temperature differential of the Defrost dinamic set point 
-30.0 
-54 
30.0 
54 
°C 
°F 
Dec 
int 
Parameter  Description  min  max  M. u.  Resolution 
rC 1  Sanitary water regulation mode  0  2     
rC 2  Recovery modes 
0 = not enabled 
1 = 2 indipendent circuit 
2 = both the circuit in parallel 
0 250 Sec  
rC 3  Delay time delay with step forced off  0  250  Sec   
rC 4  Delay time delay with step forced off after the recovery valve activation  0  250  Min   
rC 5  Recovery minimum time  0  250  Min   
rC 6  Minimum interval time between the end and the beginning of the next 
recovery 
-50.0 
-58 
0.0 
0 
110.0 
230 
50.0 
725 
°C 
°F 
Bar 
Psi 
Dec 
int 
Dec 
int 
rC 7  Temperature setpoint to disable the recovery  0.1 
0 
0.1 
1 
25.0 
45 
14.0 
203 
°C 
°F 
Bar 
Psi 
Dec 
int 
Dec 
int 
rC 8  Temperature differential to restore the recovery  0  250  Min   
rC 9  Maximum time with recovery disabled (if temperature/pressure within rC6-
rC7) 
0 1     
Parameter  Description  min  max  M. u.  Resolution 
FS 1  
Sanitary water regulation mode 
0= not enabled 
1=valves in water circuit 
2=valves in gas circuit 
0 2 
FS 2  
Sanitary water thermoregulation priority 
0  = heating / cooling 
1 = sanitary water 
2 = sanitary water by digital input 
0 2 
FS 3  
Sanitary water thermoregulation set point 
FS05 FS06 °C/°F  dec/int 
FS 4  
Sanitary water thermoregulation band 
0.1 
0 
25.0 
45 
°C 
°F 
Dec 
int 
FS 5  
Minimum value of the sanitary water set point 
-50.0 
-58 
FS06 
°C 
°F 
Dec 
int 
FS 6  
Maximum value of the sanitary water set point 
FS05 
110.0 
230 
°C 
°F 
Dec 
int 
FS 7  
Full loads enabling to reach the sanitary water set point 
0 1     
FS 8  
Heaters enabling during the sanitary water thermoregulation 
0= not enabled 
1= compressors + heaters 
2= only heaters 
3= only compressors 
0 1     
FS 9  
Operation working time to activate the heaters during the sanitary water 
thermoregulation 
0 250 Min   
FS 10   
Time delay to activate the sanitary water valve 
0 999 sec  int 
FS 11   
Reversing cycle delay during sanitary water thermoregulation 
0 999 sec  int 
FS 12   
Antilegionella function operating mode 
0 = interval time 
1= weekly 
2= daily 
0 2     
FS 13   
Delay time between two Antilegionella cycles 
0 250 Hr  0 
FS 14   
Antilegionella Set point 
FS15 FS16 °C/°F  dec/int 