Technical data

Ichill 200CX EVO rev 1.1 14/11/2013
Pag. 132 of 151
dF 11 Temperature setpoint for combined defrost end of the 1st circuit. -50.0
-58
110.0
230
°C
°F
Dec
int
dF 12 Temperature setpoint for combined defrost of the 2nd circuit after parameter
DF10 counting.
-50.0
-58
110.0
230
°C
°F
Dec
int
dF 13 Temperature setpoint for combined defrost end of the 2nd circuit. -50.0
-58
110.0
230
°C
°F
Dec
int
dF 14 Activation of all the steps of the 1st circuit during the defrost.
0= Not enabled
1= Enabled
0 1
dF 15 Activation of all the steps of the 2nd circuit during the defrost.
0= Not enabled
1= Enabled
0 1
dF 16 Time delay between two compressor ON in defrost mode 0 250 Sec
dF 17 Fan control during defrost / dripping time
0= Not enabled
1= Only in defrost
2= For both functions defrost / dripping time
0 2
dF 18 Pressure / temperature setpoint to force the ventilation ON during the defrost. -50.0
-58
0.0
0
110.0
230
50.0
725
°C
°F
bar
psi
Dec
int
Dec
Int
dF 19 Minimum time delay before a forced defrost 0 250 sec
dF 20 Pressure / temperature setpoint for a forced defrost -50.0
-58
0.0
0
110.0
230
50.0
725
°C
°F
bar
psi
Dec
int
Dec
int
dF 21 Forced defrost differential 0.1
0
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
dF 22 Defrost start-up with 2 circuits
0= Independent
1= If both have reached the necessary requirements
2= If one has reached the necessary requirements
0 2
dF 23 End defrost for two circuits and common ventilation.
0= Independent
1= If both have reached the necessary end defrost requirements
2= If one has reached the necessary end defrost requirements
0 2
dF 24 Start / stop defrost probe
0= start and stop with condenser temperatur / pressure probe
1= start with evaporator pressure probe / stop with condenser temperatur /
pressure probe
2= start with condenser temperatur / pressure probe / stop with evaporator
pressure probe
3= start and stop with evaporator pressure probe
0 3
dF 25 Stop supply fan diuring defrost cycle
0= Not enabled
1= enable
0
1
dF 26 Set point to enable defrost with condenser fan
-50.0
-58
0.0
0
110.0
230
50.0
725
°C
°F
bar
psi
Dec
int
Dec
int
dF 27
Hybrid exchangers set point 1 in chiller
-50.0
-58
0.0
0
110.0
230
50.0
725
°C
°F
bar
psi
Dec
int
Dec
int
dF 28
Hybrid exchangers set point 2 in chiller
-50.0
-58
0.0
0
110.0
230
50.0
725
°C
°F
bar
psi
Dec
int
Dec
int
dF 29
Hybrid exchangers differential 1 in chiller
0.1
0
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
dF 30
Hybrid exchangers differential 2 in chiller
0.1
0
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
dF 31
Hybrid exchangers set point 1 in heat pump
-50.0
-58
0.0
0
110.0
230
50.0
725
°C
°F
bar
psi
Dec
int
Dec
int
dF 32
Hybrid exchangers set point 2 in heat pump
-50.0
-58
0.0
0
110.0
230
50.0
725
°C
°F
bar
psi
Dec
int
Dec
int