dF 11    Temperature setpoint for combined defrost end of the 1st circuit.  -50.0 
-58 
110.0 
230 
°C 
°F 
Dec 
int 
dF 12    Temperature setpoint for combined defrost of the 2nd circuit after parameter 
DF10 counting. 
-50.0 
-58 
110.0 
230 
°C 
°F 
Dec 
int 
dF 13    Temperature setpoint for combined defrost end of the 2nd circuit.  -50.0 
-58 
110.0 
230 
°C 
°F 
Dec 
int 
dF 14    Activation of all the steps of the 1st circuit during the defrost. 
0= Not enabled 
1= Enabled 
0 1     
dF 15    Activation of all the steps of the 2nd circuit during the defrost. 
0= Not enabled 
1= Enabled 
0 1     
dF 16    Time delay between two compressor ON in defrost mode  0  250  Sec   
dF 17    Fan control during defrost / dripping time 
0= Not enabled 
1= Only in defrost 
2= For both functions defrost / dripping time 
0 2     
dF 18    Pressure / temperature setpoint to force the ventilation ON during the defrost.  -50.0 
-58 
0.0 
0 
110.0 
230 
50.0 
725 
°C 
°F 
bar 
psi 
Dec 
int 
Dec 
Int 
dF 19    Minimum time delay before a forced defrost  0  250  sec   
dF 20    Pressure / temperature setpoint for a forced defrost  -50.0 
-58 
0.0 
0 
110.0 
230 
50.0 
725 
°C 
°F 
bar 
psi 
Dec 
int 
Dec 
int 
dF 21    Forced defrost differential  0.1 
0 
0.1 
1 
25.0 
45 
14.0 
203 
°C 
°F 
Bar 
Psi 
Dec 
int 
Dec 
int 
dF 22    Defrost start-up with 2 circuits 
0= Independent 
1= If both have reached the necessary requirements 
2= If one has reached the necessary requirements 
0 2    
dF 23    End defrost for two circuits and common ventilation. 
0= Independent 
1= If both have reached the necessary end defrost requirements 
2= If one has reached the necessary end defrost requirements 
0 2    
dF 24    Start / stop defrost probe 
0= start and stop with condenser temperatur / pressure probe 
1= start with evaporator pressure probe / stop with condenser temperatur / 
pressure probe 
2= start with condenser temperatur / pressure probe / stop with evaporator 
pressure probe 
3= start and stop with evaporator pressure probe 
0 3    
dF 25    Stop supply fan diuring defrost cycle 
0= Not enabled 
1= enable 
0
1 
dF 26    Set point to enable defrost with condenser fan 
-50.0 
-58 
0.0 
0 
110.0 
230 
50.0 
725 
°C 
°F 
bar 
psi 
Dec 
int 
Dec 
int 
dF 27   
Hybrid exchangers set point 1 in chiller 
-50.0 
-58 
0.0 
0 
110.0 
230 
50.0 
725 
°C 
°F 
bar 
psi 
Dec 
int 
Dec 
int 
dF 28   
Hybrid exchangers set point 2 in chiller 
-50.0 
-58 
0.0 
0 
110.0 
230 
50.0 
725 
°C 
°F 
bar 
psi 
Dec 
int 
Dec 
int 
dF 29   
Hybrid exchangers differential 1 in chiller 
0.1 
0 
0.1 
1 
25.0 
45 
14.0 
203 
°C 
°F 
Bar 
Psi 
Dec 
int 
Dec 
int 
dF 30   
Hybrid exchangers differential 2 in chiller 
0.1 
0 
0.1 
1 
25.0 
45 
14.0 
203 
°C 
°F 
Bar 
Psi 
Dec 
int 
Dec 
int 
dF 31   
Hybrid exchangers set point 1 in heat pump 
-50.0 
-58 
0.0 
0 
110.0 
230 
50.0 
725 
°C 
°F 
bar 
psi 
Dec 
int 
Dec 
int 
dF 32   
Hybrid exchangers set point 2 in heat pump 
-50.0 
-58 
0.0 
0 
110.0 
230 
50.0 
725 
°C 
°F 
bar 
psi 
Dec 
int 
Dec 
int 